Siemens Siprotec 7UM62 Manual page 288

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Functions
Settings on the
Thermobox
Further Processing
of Measured Values
and Indications
272
The location RTD1 is communicated to the device at address 9012A RTD 1 LOCA-
TION. Setting options are Oil, Ambient, Winding, Bearing and Other. This set-
ting is only possible with DIGSI
You can also set an alarm temperature and a tripping temperature. Depending on the
temperature unit selected in the power system data (Section 2.3 at address 0276
TEMP. UNIT), you can select the alarm temperature at address 9013 RTD 1 STAGE
1 in degree Celsius (°C) or at address 9014 RTD 1 STAGE 1 in degree Fahrenheit
(°F). The tripping temperature is set at address 9015 RTD 1 STAGE 2 in degree
Celsius (°C) or at address 9016 RTD 1 STAGE 2 in degree Fahrenheit (°F).
In the same way, you can make the settings for all connected temperature detectors
(see the settings table in 2.42.2.1).
Where temperature detectors with a 2-wire line are used, the line resistance must be
measured and set (with the temperature detector shorted). To do so, select mode 6 in
the thermobox and enter the resistance value for the desired detector (range 0 to
50.6 Ω). For temperature detectors with a 3-wire line, no extra settings are required.
The information is exchanged with a baud rate of 9600 bits/s. The parity is even. The
bus number is set to 0 in the factory. Changes can be made in mode 7 on the ther-
mobox. The following convention applies:
Table 2-18
Setting the Bus Address on the Thermobox
Operation
Number of Thermoboxes
Simplex
Half-duplex
Half-duplex
More information can be found in the operating instructions supplied with the ther-
mobox.
The thermobox is seen in DIGSI
cations and measured values appear in the configuration matrix just like those of in-
ternal functions, and can be masked and processed in the same way. This means that
indications and measured values can also be transmitted to the integrated user-defin-
abled logic (CFC) and linked in any desired way.
If you want an indication to appear in the operational indication buffer, mark the matrix
cell at the appropriate column/line intersection with a cross.
®
4 under "Advanced Parameters".
Address
1
1
1st thermobox: 1
2
2nd thermobox: 2
®
4 as part of the 7UM62 protection device, i.e. indi-
0
1
7UM62 Manual
C53000-G1176-C149-3