Siemens Siprotec 7UM62 Manual page 418

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

4 Technical Data
EMC Tests For
Noise Emission
(Type Test)
402
– Irradiation with HF Field,
Non-Modulated
IEC 60255–22–3 (Report) Class III
– Irradiation with HF Field,
Amplitude Modulated
IEC 61000–4–3, Class III
– Irradiation with HF Field,
Pulse Modulated
IEC 61000–4–3/ENV 50204, Class III
– Fast Transient Disturbance Variables/ 4 kV: 5/50 ns: 5 kHz: Burst length = 15 ms;
Burst IEC 60255–22–4 and
IEC 61000-4-4, Class IV
– High Energy Surge Voltages
(SURGE), IEC 61000–4–5
Installation Class 3
Power Supply
Measuring Inputs, Binary Inputs
and Relay Outputs
– Line Conducted HF, Amplitude Modul. 10 V: 150 kHz to 80 MHz: 80 % AM: 1 kHz
IEC 61000–4–6, Class III
– Power System Frequency Magnetic
Field IEC 61000–4–8, Class IV
IEC 60255–6
– Oscillatory Surge Withstand Capability 2.5 to 3 kV (Peak Value): 1 MHz to 1.5 MHz
ANSI/IEEE C37.90.1
– Fast Transient Surge Withstand Cap. 4 kV to 5 kV: 10/150 ns: 50 Pulse per s;
ANSI/IEEE C37.90.1
– Radiated Electromagnetic Interference 35 V/m: 25 MHz to 1000 MHz
ANSI/IEEE C37.90.2
– Damped Oscillations
Similar to IEC 60694–4–12,
IEC 61000–4–12
Standard:
– Radio Noise Voltage to Lines,
Only Power Supply Voltage
IEC–CISPR 22
– Radio Noise Field Strength
IEC–CISPR 11
10 V/m: 27 MHz to 500 MHz
10 V/m: 80 MHz to 1000 MHz: 80 % AM:
1 kHz
10 V/m: 900 MHz: repetition frequency
200 Hz: duty cycle of 50 %
repetition rate 300 ms: both polarities:
= 50 Ω: Test Duration 1 min
R
i
1.2/50 µs
2 kV: 12 Ω: 9 µF
common mode:
1 kV: 2 Ω: 18 µF
diff. mode:
2 kV: 42 Ω: 0.5 µF
common mode:
1 kV: 42 Ω: 0.5 µF
diff. mode:
30 A/m continuous: 300 A/m for 3 s: 50 Hz
0.5 mT: 50 Hz
damped wave: 50 surges per s:
= 150 Ω to 200 Ω
duration 2 s: R
i
both polarities: Duration 2 s: R
amplitude and pulse modulated
2.5 kV (Peak Value), polarity alternating
100 kHz, 1 MHz, 10 MHz and 50 MHz,
= 200 Ω
R
i
EN 50081 (Generic Standard)
150 kHz to 30 MHz
Limit Class B
30 MHz to 1000 MHz
Limit Class A
= 80 Ω
i
7UM62 Manual
C53000-G1176-C149-3

Advertisement

Table of Contents
loading