1.1.3
Stop Data Transmission
Reference
1.2
Commands
1.2.1
Single Commands
Reference
1.2.2
Changing the setting group
Reference
7SJ61 / 7SJ62 / 7SJ64 Bus mapping
C53000-L2540-A306-2
The functionality "Stop data transmission" is not supported via IEC 60870-5-103 com-
munication. If "Stop data transmission" is active nevertheless data via IEC 60870-5-
103 will be transmitted furthermore.
The annunciation "DataStop" (Obj.- Adr. 16) signals the activation of "Stop data trans-
mission" however and can be evaluated correspondingly in the IEC 60870-5-103 mas-
ter.
ref. to chap. 3.2.8
Note
The allocation of the output relays to the switching devices and to the binary outputs
is defined during parametrization of the SIPROTEC devices.
Depending on the device composition there may be less than the indicated output re-
lays (and corresponding IEC 60870-5-103 Information numbers) available in the
SIPROTEC device.
The command output mode (pulse output, continuous output) is changeable for the
single commands using parametrization software DIGSI 4.
The switching direction OFF for single commands with pulse output is not permitted
and is rejected in the SIPROTEC device.
ref. to chap. 3.1.2
Switching on one setting group automatically switches off the current active setting
group. Transmission of the value OFF is insignificant for the change of the setting
group and is refused by the device.
A change of the setting group is only possible via IEC 60870-5-103 if the parameter
C
A
S
HANGE TO
NOTHER
tocol".
Refer to chapter 3.1.2 to the command for changing the setting group. The indication
for a change of a setting group is shown in chapter 3.2.8
(parameter address = 302) has the value "Pro-
G
ETTING
ROUP
Notes to SIPROTEC objects
13