Bosch Rexroth AG
Device description
Fig. 12-17: Selecting the target directory to save the core dump
After selecting a valid target directory, press Save to start saving the core
dump. If saving was successful, a corresponding status message is shown.
The dialog can now be closed. After closing the dialog, the core dump is
displayed with its respective data.
12.6 Backing up remanent data
128 KB of remanent data is automatically backed up in an internal flash memory
after a 24 V supply voltage failure and restored at control startup.
12.7 Real-time clock
The real-time clock of the control is buffered in the switched-off state. The buf-
fer capacitor looses efficiency when operated permanently at high tempera-
tures. The buffer time of the real-time clock depends on the ambient tempera-
ture and the operating time of the control.
Operating time of the control at ambient temperature
5 years at 50 °C permanent
7 years at 50 °C permanent
10 years at 50 °C permanent
2.5 years at 60 °C permanent
52/61
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Buffer time of the clock
①
Typ. 10 days
Typ. 7 days
Typ. 4 days
Typ. 10 days
DOK-CONTRL -IC*XM2*****-IT03-EN-P
Controls