NOTICE
The XM2x control contains components that can be damaged or destroyed by
electrostatic discharge. Comply with the required safety measures against elec-
trostatic discharge (ESD) acc. to EN 61340-5-1 when operating the control.
Mounting location
●
The XM2x control has the degree of protection IP20 and is thus intended for
the use in a closed control cabinet or control box (terminal box) of the degree
of protection IP54 or higher.
Mounting rail
●
Mount the XM2x control on a 35 mm standard mounting rail. The preferred
overall height of the mounting rail is 7.5 mm (corresponds to TH 35-7.5 acc.
to EN 60715).
Mount the control and the bus base module as described in the following.
The fastening distance of the mounting rails may not exceed 200 mm. This
distance is required to ensure stability while mounting and demounting the
control or the S20 I/O modules.
Fig. 10-1: Mounting rail fastening (in mm)
NOTICE
If the fastening elements (screws, rivets,...) are too high, the bus base mod-
ules do not correctly engage on the mounting rail. Use only elements with a
structural height of up to 3 mm to fasten the mounting rail.
End clamp
●
Fasten end clamps on both sides of the IndraControl XM station (control, ex-
tension modules, S20 I/O modules).
16/61
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
chapter 5 "Spare parts, accessories
5).
Module destruction due to electrostatic dis-
charge
Electronic damage due to fastening elements
Danger of malfunction
Controls
_
< 200
DOK-CONTRL -IC*XM2*****-IT03-EN-P