Commissioning
1. Mount the control.
For details, refer to
lation" on page
2. Connect the voltage supply to the XD1 connection of the control.
Refer to
chapter 10.7.2 "Voltage supply for the control" on page
3. Switch on the control → The initial firmware starts.
Refer to
chapter 12.2.3 "Starting and opening the initial firmware" on page
40.
4. Install the system firmware. There are two options:
Via IndraWorks (refer to the functional description of the respective sys-
tem (IndraMotion MLC, IndraMotion MTX)
Via the initial firmware (refer to
38).
5. Start the commissioning tool "IndraControl First Touch" and make the cor-
responding settings (IP address, subnet mask, gateway address).
Refer to
chapter 12.5 "IndraControl First Touch" on page
NOTICE
Note that hardware is initialized after switching on the control and after instal-
ling the system firmware with subsequent reboot. An internally programmable
function block is loaded. After loading, the LED display "ON" at the voltage plug
is green.
Wait till completion. Do not switch off the control. This procedure has to be
completed. Subsequently, continue the commissioning.
11.2 Establishing a connection to the engineering PC via the USB
device interface "XF31"
Instead of using the Ethernet interface "XF5" to commission the control or to
use the commissioning tool "IndraControl First Touch", use the connection XF31.
Connect the USB interface of your computer to the USB device connection
"XF31" via a common USB data and charging cable. Upon the initial connection,
the respective device driver (USB Remote NDIS) is installed on the PC.
Even though the computer and the control communicate via Ethernet, it is only a
point-to-point connection.
The IP address of the connection "XF31" on the control is
192.168.234.234.
The IP address cannot be changed.
If the RNDIS device driver is not installed automatically, install it manually:
30/61
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
chapter 10 "Mounting, demounting and electric instal-
16.
Control malfunction due to control switch-off
during initialization
chapter 12.2 "Initial firmware" on page
DOK-CONTRL -IC*XM2*****-IT03-EN-P
Controls
25.
43.