Controls
End clamps guarantee the correct fastening of the XM2x control and the S20
I/O modules connected to them on the mounting rail and they are used as lat-
eral end elements.
Always fasten the left end clamp of the station before mounting the control.
This ensures the following:
– It impedes the shifting of the control.
– The installation place for the end clamps is guaranteed.
– If the control has to be replaced, there is sufficient space to separate the
control from the S20 bus base modules.
– They have a counterpressure against the engaging forces when mounting
the S20 bus base modules in series to the control.
Do not wire cables parallel to motor cables or other strong interference sour-
●
ces to avoid coupling of interferences
The cabling of the Ethernet wires may not leave the building
●
The LED displays on the operating panel must not be covered
●
Observe the bending radius of the cables used when laying the connecting
●
lines
Use strain reliefs for all cables
●
Install the control only horizontally on a mounting rail attached to a wall
●
Keep the maximum distance possible from interference sources
●
Provide the following minimum distances for sufficient cooling:
●
30 mm
Fig. 10-2: Minimum distances for the circulation of ambient air
DOK-CONTRL -IC*XM2*****-IT03-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Mounting, demounting and electric installation
100 mm
30 mm
100 mm
Bosch Rexroth AG
30 mm
17/61