8.1.2

Serial Communication

As per order reference, the SICAM I/O Unit has a serial FO or RS485 interface and can therefore communicate
in series with peripheral devices via Modbus RTU. The serial interface supports:
Transfer of messages
Time Synchronization
Data exchange between 2 SICAM I/O Units via Modbus RTU as point-to-point I/O mirror
Data of the RS485 Interface when Using the Modbus RTU Protocol
The RS485 interface comes with the following parameters set by the manufacturer:
Bus protocol:
Device address:
Baud rate:
Parity:
Access rights:
Communication supervision time:
You can modify these parameters during the parameterization, see chapter 6.3.3.8.
The connection is a 9 pin D-sub connector plug.
Data of the FO Interface when Using the Modbus RTU Protocol
The FO interface comes with the following parameters set by the manufacturer:
Bus protocol:
Device address:
Baud rate:
Parity:
Access rights:
Communication supervision time:
Fiber optical idle state:
You can modify these parameters during the parameterization, see chapter 6.3.3.8.
The connection is a ST connector BFOC/2.5 for sending and receiving, 820 nm.
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Modbus RTU
1
19 200 bit/s
Even
Full
1 min
Modbus RTU
1
19 200 bit/s
Even
Full
1 min
Light off