Page 1
Preface Contents User Information SICAM I/O Unit Overview Device Design 7XV5673 Getting Started Applications Device Manual Operation Time Synchronization Communication Maintenance, Storage, Transport Failures and LED Indications Technical Data Operational Indications Operating Parameters Glossary Index E50417-H1040-C484-A3...
Page 2
, and SICAM are registered trademarks of Siemens AG. An unauthorized use is illegal. Siemens AG reserves the right to revise this document from time to time. All other designations in this document can be trademarks whose use by third parties for their own purposes can infringe the rights of the owner.
This manual is intended for project engineers, commissioning and operating personnel in electrical systems and substations. Scope of validity of this manual This manual is valid for the SICAM I/O Unit 7XV5673. Further support For any questions concerning your system, please contact your Siemens representative.
Page 4
Follow all advice instructions to prevent damage to property. NOTE is important information about the product, the handling of the product, or the part of the documentation in question to which special attention must be paid. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 5
Equipment with current transformer circuits must not be operated while open. • The limit values indicated in the manual and the product information must not be exceeded; this also refers to testing and commissioning SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 6
Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Lowvoltage Directive 2006/95/EC). This conformity has been established by means of tests conducted by Siemens AG in accordance of the Council Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for the EMC directives, and with the standard EN 60255-27 for the low-voltage directive.
User Information Application Scope SICAM I/O Unit 7XV5673 is a digital input/output device and is used by utilities (energy supply companies) in substation environment. The device is also used for industrial sectors and in businesses with increased envi- ronmental requirements. It can be used in nearly every application for protection relays or SCADA, e.g. over current protection, teleprotection or Substation Automation.
Page 12
External time synchronization via Ethernet NTP • External time synchronization via fieldbus with Modbus RTU, Modbus TCP or Modbus UDP communica- tion protocol • Internal time synchronization via RTC (if there is no external time synchronization) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Overview Versions of SICAM I/O Unit Ordering Information, Scope of Delivery and Accessories SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
2.1 Versions of SICAM I/O Unit Versions of SICAM I/O Unit SICAM I/O Unit 7XV5673 is an input/output device for digital signals. It consists of modules that perform the detection and implementation of signals for the relay outputs. Uniform Device Properties All device variants have the following uniform properties: •...
Order Information Scope of Delivery Included in delivery are: • SICAM I/O Unit 7XV5673 according to order reference (see Figure 2-1) • PANASONIC C2032 or VARTA 6032 101 501 battery (contained separately in the battery compartment of the device) •...
Page 16
6XV1 830-0EH10 (minimal order quantity 20 m) Length preferred 20 m 6XV1 830-0EN20 Length preferred 50 m 6XV1 830-0EN50 Length preferred 100 m 6XV1 830-0ET10 Length preferred 200 m 6XV1 830-0ET20 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 17
Ordering information for prepared optical fiber cables (fiber-optic cable) is available on the Internet (SIPROTEC download area) under http://www.siprotec.com under accessories -> 6XV81xx. • Further notes on device accessories and their environment can be found under http://www.siprotec.com. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 18
2 Overview 2.2 Ordering Information, Scope of Delivery and Accessories SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
IP address and the default subnet mask are imprinted on the side panel. 7XV5673-0JJ20-1AA1 7XV5673-0JJ10-1AA1 7XV5673-0JJ00-1AA1 Figure 3-1 Design of the SICAM I/O Unit 7XV5673 with RS485 and Serial FO Interface or without Serial Interface SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Getting Started Unpacking, Inspecting the Delivery and Installing the Battery Assembly Electrical Connection System Requirements Access Rights Meaning of the LEDs Commissioning SICAM I/O Mapping Tool Installation SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Lever the cover of the battery compartment out of the socket with a suitable tool (e.g. precision engineer screwdriver 2.0 mm). Cover of battery Polarity of compartment the battery Figure 4-1 Top Side of the SICAM I/O Unit SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
The SICAM I/O Unit is intended to be installed on a hat rail, for example in a control cabinet. WARNING Do not touch any voltage-carrying parts. Non-observance may lead to death or serious injury. ✧ After installation of the device and wiring, close the control cabinet. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Subsequently, press the release device back into its guiding. UL-certification conditions Field Wires of Control Circuits shall be separated from other circuits with respect to the end use requirements! SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
• To allow temperature equalization and to avoid dimness and condensation, Siemens recommends leaving the device for a minimum of 2 hours in the operating room before using it. NOTE Before switching on the supply voltage, please check whether the operational data comply with the rated data on the name plate and the technical data according to chapter 11.1.
SICAM I/O Unit 7XV5673-0JJ10-1AA1. Terminal blocks N, P Terminal connection of the supply voltage Figure 4-3 Supply Voltage Terminals and Terminal Blocks on the SICAM I/O Unit 7XV5673-0JJ10-1AA1 DANGER Hazard posed by high contact voltage. Non-observance leads to death or serious injury. ✧...
NOTE If you do not set up new passwords, the passwords automatically implemented by default (see chapter 6.3.3.9) will be valid. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
LED on: Ethernet link is up LED flashing: Ethernet link is up and data are transferred LED off: no Ethernet devices connected Speed LED on: 100 Mbit/s LED off: 10 Mbit/s SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Switch on the supply voltage of the device. NOTE The device does not have a power on/off switch. The supply voltage must be switched on or off directly at the respective supply cable. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
In this case, the parameterized IP address and the default IP address are displayed on the Information tab, Device information item (see chapter 6.2.5.1). When the device has started with the default IP address, the factory-set default passwords are also active (see chapter 6.3.3.9). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Select a folder in which the program is to be stored, and specify whether the installation is to be made just for you or also for other users. Figure 4-7 Select Installation Folder SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 35
Click the Next button in this and also in the subsequent window. Figure 4-8 Confirm Installation ✧ When the program has been installed successfully, click the Close button to exit the installation. Figure 4-9 Installation Complete SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 36
4 Getting Started 4.8 SICAM I/O Mapping Tool Installation SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
• Optical Repeater 7XV5461 • RS485-FO Converter 7XV5650 • Communication Converter 7XV5662 (KU-KU, X.21/G.703.1, G.703.6). NOTE Please note additional time delays of devices (see their documentation) within the transmission route. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
If using n devices, up to n × 6 relay outputs can be used. NOTE A star coupler is required for serial optical transmission. Also compare Figure 5-8 with optical repeaters. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
I/O Expansion for the Connection to Systems Control, Using Integrated Switch NOTE In this application, the SICAM I/O Unit can only be operated in multipoint-partyline configuration. Operation in multipoint-ring configuration is not possible. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 41
Ethernet switch in the SICAM I/O Unit. NOTE The I/O expansion application can also be electric via serial communication (for example RS485 Bus System 7XV5103) or FO (for example Star Coupler 7XV5450) with Modbus RTU protocol. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
ST plugs, max. 1.5 km Modbus server Indication Relay outputs from Remote Binary inputs optical interfaces of SICAM I/O Units Figure 5-4 I/O Expansion for the Connection to Systems Control, Using Mini Star Couplers SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Several binary signals get to the relay module via the selected binary inputs of the SICAM I/O Unit. Depending on parameterization, they are assigned simultaneously and parallel to the parameterized relay outputs. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
The asynchronous baud rate of the binary signal transmission depends on the available synchronous band width of the transmission route. This also essentially influences transmission time. A maximum of 6 binary single signals can be transmitted bidirectionally. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
A typical application is the directional comparison of a directional overcurrent protection via economical pilot wires, where the definite time-overcurrent protection is connected to the binary signal transmission via con- tact and binary input. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Additionally, for evaluation purposes, the locations of the remote circuit-breakers and separators can be transmitted in the local device. This makes the realization of smart grid applications across large distances possible in order to exchange interference-free binary signals. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
(2 FO, 1 RS232) of the KU-2M, a maximum of 18 individual signals can be exchanged bidi- rectionally. Siemens recommends the 7XV5100-4 cable (DIGSI cable) with gender changer (9 pin male/male) as RS232 - KU-2M connecting cable.
Modbus UDP protocol. When connecting via routed network components, the ports for the protocol have to be released. An encryption of the data on unsecured IP networks has to be performed via external devices. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Operation General Usage Notes Start and Design of the User Interface Configuration of the Device Value View Maintenance Examples for Parameterization SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
List box: selects an item from a list Button: a click on the button executes an action Active tab (light blue) Inactive tab (dark blue) Selects and opens the item to be activated, for example a tab SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Enter the IP address in Microsoft Internet Explorer (for example default IP Address: 192.168.0.55) of the SICAM I/O Unit and press Enter. The user interface opens with the Information tab → Show device information (see Figure 6-4). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Click the Tools menu on the menu bar of Microsoft Internet Explorer. ✧ Select Internet options... from the Tools menu. ✧ In the Internet Options dialog open the Security tab. Figure 6-2 Enabling JavaScript SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Default Level button and set the scroll bar that appears to Medium. ✧ Click the Apply button. ✧ Click the OK button. 6.2.3 Number of Connections via HTTP 3 users maximum can connect with the device via HTTP. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
The user interface has the following layout: Address bar Microsoft Internet Explorer Online help Menu bar Toolbar Navigation bar Navigation window Menu Element Input/output window Status bar Figure 6-3 Designation in the User Interface SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
The navigation window of the Information tab contains the elements Show Device Information, Save device information and message logs and the Message Logs menu with the elements Operational log and Error log. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 56
Information Tab, Save Device Information Input/Output Save Device Information and Logs as Text File ✧ Click the Save .TXT button The File Download dialog opens. Figure 6-6 File Download Dialog, Save .TXT SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 57
The list is printed on the connected printer. ✧ Close the text editor. ✧ Click an element on the navigation window or a tab, or alternatively, click the Back icon on the toolbar of Microsoft Internet Explorer twice. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 58
Use the file name suggested in the File name: list box or enter a new file name with the file extension .CSV. ✧ Click the Save button. The Download complete dialog opens. ✧ In the Download complete dialog, click the Close button. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 59
Date of registration − Time of registration − Information on the indication − Value of the indication On, Off or invalid − Cause source of the indication (for example Internal, Browser) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 60
Task, Code and Location are service information for the manufacturer − Description of the error NOTE The error messages can be printed as described in chapter 6.2.5.2. The chapter 6.5.3.2 explains how to delete the error messages manually. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
If you have not changed the parameter set since the first start of the device (see chapter 6.2.1), use the default settings. To change the settings of the parameter set, proceed as follows: ✧ Click the Configure tab on the user interface The Configure tab opens. Figure 6-12 Configure Tab SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 62
Activate the modified configuration as described in chapter 6.3.1.3. Get Default Configuration and Editing ✧ Click the Get default configuration button. A copy of the factory settings (= passive parameter set) of the device is opened for editing. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 63
If you have selected Open configuration from file in the Configure tab, you can open an already existing file in a folder. Proceed as follows: Figure 6-14 Configure Tab, Open Configuration from File ✧ Click the Browse... button. The Choose file dialog opens. Figure 6-15 Choose File SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 64
The modified parameter set is loaded as the active parameter set into the device and the new parameters take effect immediately. If the password is wrong, this message appears: The password is wrong. Please enter the correct password.. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 65
The Save Configuration to File input/output window opens. Figure 6-17 Configure Tab, Save Configuration to File Input/Output Window ✧ Click either of the buttons Save active configuration or Save passive configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 66
Use the file name suggested in the File name: list box or enter a new file name with the file extension .CFG. ✧ Click the Save button. The Download complete dialog opens. ✧ In the Download complete dialog, click the Close button. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 67
Get device configuration → Get active configuration described in chapter 6.3.1.1. When you have clicked the Cancel button, the parameterization is released and can be run from a different computer if necessary. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
If the user has completed his changes to the passive parameter set or finished the parameterization by clicking the Cancel button, write access for all users is also released. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
2-ms steps) Binary input indication For example for terminal P8/9: Arbitrary text; name of (can be set for all binary inputs individually) Binary input 1 - terminal block P the indication SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 70
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 71
In the navigation window, select the Operational menu, then the Process connections submenu and click Binary outputs. The Binary outputs input/output window opens. Figure 6-23 Configure Tab, Binary Outputs Input/Output Window NOTE The parameterization of both binary outputs is identical. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 72
= yes has been parameterized, the binary output switches to ON mode. Indication Indication invalid invalid Output Binary output not inverted Binary output inverted Output Figure 6-25 Persistent with Fail Save SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 73
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 74
To change the outputs of the LEDs H1, H2 and ERROR, proceed as follows: ✧ In the navigation window, select the Operational menu, then the Process connections submenu and click LEDs. The LEDs input/output window opens. Figure 6-28 Configure Tab, LEDs Input/Output Window SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 75
6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. Behavior of the LEDs Indication Indication invalid invalid flash flash Figure 6-29 Behavior of the LEDs SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 76
✧ In the navigation window, select the Operational menu, then the Administrative submenu and click Indication properties. The Indication properties input/output window opens. Figure 6-30 Configure Tab, Indication Properties Input/Output Window SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 77
Secondary NTP server IP address 192.168.0.253 Error indication after 10 min 2 min to 120 min Additional parameter if the source is Fieldbus (Modbus RTU) Error indication after 10 min 2 min to 120 min SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 78
Select the time difference to UTC in the DST offset to UTC list box. ✧ In the list boxes under Start of DST specify the month, week, day and time for starting Daylight Saving Time. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 79
Select the time difference to UTC in the Time zone offset to UTC list box. ✧ The option buttons at Daylight Saving Time switchover allow you to enable (yes) or disable (no) the automatic Daylight Saving Time adjustment. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 80
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 81
(can be parameterized, if no I/O mirror mode is selected under Communication Serial) Port number 51000 10000 to 65535 Communication supervision time 8 *10 ms 0 ms = invalid 10 ms to 60 000 ms SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 82
4) The parameters stated here are only used when yes is selected for “Use settings in the table below“ (see Figure 6-36). This allows for a simple configuration of the GOOSE publishers without using DIGSI and the SICAM I/O Mapping Tool. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 83
If you select -none-, there will be no log and no mode available. In this case, click the Send button. If you have selected a Modbus protocol or an Operating mode, parameterize as follows: SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 84
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 85
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 86
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 87
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 88
Before uploading the Subscriber configuration, please make sure that the IEC 61850 GOOSE Subscriber Configuration has been executed. For uploading the Subscriber configuration, the MAP file (file extension .MAP) is required. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 89
Click the Open button (see Figure 6-37). The device configuration is loaded from the MAP file. Then, the software of the device checks which edition is configured by the file. The configuration SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 90
The Edition 2 configuration is uploaded. Edition 2 is selected in the IEC 61850 Edition list box; the configuration becomes effective immediately after having restarted the device. Figure 6-39 File Opened Successfully SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 91
6.3 Configuration of the Device Case 2: File failed to open A wrong file is selected, which has the same file extension .MAP or a different file extension. Figure 6-40 File Failed to Open SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 92
Enter the hexadecimal multicast address [xx-xx-xx-xx-xx-xx] in the Multicast MAC address field. ✧ Enter the hexadecimal App ID [xxxx] in the App ID field. ✧ Enter the hexadecimal VLAN ID [xxx] in the VLAN ID field. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 93
Mapping Tool, and a binary IEC 61850 parameter set can be created (proprietary format). The result can then be uploaded via the HTML page. NOTE The configuration requires the installation of the SICAM I/O Mapping Tool program (see chapter 4.8). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 94
Enter the same IED name as in DIGSI 4 in the SICAM I/O Mapping Tool (e.g. IED name S_IO_00002, see Figure 6-42). Figure 6-42 SICAM I/O Mapping Tool ✧ Click Load in the menu bar and load the SCD file into the SICAM I/O Mapping Tool. A validation is performed. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 95
Click Generate Mapping in the menu bar and select a folder for storing the file. In this folder, the file 7XV5673.MAP is generated. NOTE The MAP file (7XV5673.MAP) can be uploaded to the device (see section Ethernet Communication Using the IEC 61850 Bus Protocol). NOTE If there are several I/O units in the station, this process must be performed for each device.
Page 96
− lnInst: Instance number of the logical node object − doName: Instance name of the data object (DO) − daName: Name of the data attribute (DA) From these explanation results: S_IO_00001/CTRL/lnGGIO1/Ind3/stVal SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 97
0 s = invalid Communication supervision time 10 ms to 60 000 ms (Siemens recommendation, see chapter 8.3.2.2) If there is an FO interface: Light OFF Light OFF Fiber optical idle state Light ON SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 98
Enter the time in x * 100 ms into the Communication supervision time field. ✧ Click the Send button. After clicking the Send button, the parameters are transmitted to the device but not enabled yet (passive parameter set). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 99
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 100
If you do not want to change any other settings, continue with the Activation of the device configuration according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the device configuration. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 101
Enter the name of the device into Device name field. ✧ Select the user interface language in the Language list box. ✧ Select the date and time format in the Date/time format list box. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 102
The items in the Finish configuration menu in the navigation window are described in chapter 6.3.1, in these subsections: • Activating the Parameter Set • Save Configuration to File • Cancel SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Depending on the selection, the values of the binary inputs or outputs are displayed in a table in the input/output window and they are each updated after 5 s. To print out the values, click the (Print) icon on the toolbar of Microsoft Internet Explorer. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
If you want to edit this tab, you need the Maintenance password (see chapter 4.5). To open the Maintenance tab, proceed as follows: ✧ Click the Maintenance tab. The Maintenance tab opens. Figure 6-51 Maintenance Tab SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
During a firmware update, the device firmware, the default parameter set, text libraries, HTML files or parts thereof are updated. NOTE Before updating the firmware, Siemens recommends saving the current parameters set as described in chapter 6.3.1.3. To update the firmware proceed as follows: ✧...
Page 106
Device firmware, default parameter set, text libraries, HTML files or parts thereof are uploaded within one minute. The device then restarts automatically NOTE Do not switch off the supply voltage during the update process as this can lead to data loss. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Enter the maintenance password into the Password field. ✧ Click the Set Date/time button. The time you have entered is displayed in the fields of the input/output window and applied in the device. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
All operational indications in the input/output window are deleted without backup. The indication no. 00001 appears in the column Information: "Clear Operational Log". NOTE If you need the operational indications, for example for subsequent analysis, save or print them out as described in chapter 6.2.5.2. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 109
All error messages in the input/output window are deleted without backup. The indication no. 00001 appears in the column Description: ***Error Log Cleared***. NOTE If you need the error messages, for example for subsequent analysis, save or print them out as described in chapter 6.2.5.2. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
To clear the counters for Modbus TCP, click the Clear counters button in the Modbus TCP section of the input/output window. All counters in the Modbus TCP section are reset to zero. NOTE The chapter 8.2.9.1 gives more details about diagnosing Modbus. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 111
To clear the counters for Modbus UDP, click the Clear counters button in the Communication Ethernet section of the input/output window. All counters in the Modbus UDP section are reset to zero. NOTE The chapter 8.2.9.2 gives more details about diagnosing Modbus. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 112
To clear the counters for Modbus RTU, click the Clear counters button in the Modbus RTU section of the input/output window. All counters in the Modbus RTU section are reset to zero. NOTE The chapter 8.2.9.3 gives more details about diagnosing Modbus. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 113
NOTE For further information regarding the diagnosis of I/O Mirror via Ethernet, refer to chapter 8.3.3.1 (Communica- tion Ethernet, I/O Mirror Client) and in chapter 8.3.3.2 (Communication Ethernet, I/O Mirror Server). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 114
All counters in the Communication Serial section are reset to zero. NOTE For further information regarding the diagnosis of the serial I/O mirror, refer to chapter 8.3.3.3 (Communication Serial, I/O Mirror Client) and in chapter 8.3.3.4 (Communication Serial, I/O Mirror Server). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 115
The IEC 61850 input/output window opens and the protocol is displayed. The Ethernet interface is then analyzed. Fig. 6-63 Maintenance Tab, Diagnosis IEC 61850 Input/output Window NOTE The chapter 8.4.4 provides more details on diagnosing IEC 61850. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
When assigning the IP address make sure that this address is only assigned once in the communication network (see chapter 6.2.1). Parameterization is always via the Ethernet interface – locally or via communication. Binary inputs and outputs that are not connected are insignificant for the parameterization. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Use the hardware configuration according to Figure 5-3 without I/O expansion. Factory Setting of the Ethernet Communication via Modbus TCP NOTE Please note the Modbus data mapping in chapter 8.2.8. Figure 6-64 Default Setting Ethernet Communication SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 118
Setting of the 6 Binary Inputs with Different Threshold Value Voltages Figure 6-65 Settings of the 6 Binary Inputs Routing of Indications from Remote to the 6 Binary Outputs with Various Modes Figure 6-66 Settings of the 6 Binary Outputs SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Parameterize the threshold value voltages of the binary inputs according to Figure 6-65. Routing of Indications from Remote to the 6 Binary Outputs ✧ Parameterize the indications and modes of the binary outputs according to Figure 6-66. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Route the Indications from Remote to the 6 Binary Outputs of the SICAM I/O Unit – Server ✧ Parameterize the indications and modes of the binary outputs according to Figure 6-66. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 121
Please note, that when parameterizing the SICAM I/O Unit – client, its IP address has to differ from the Server IP address of the SICAM I/O Unit – server. If necessary, change the IP address of the SICAM I/O Unit – client. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Route the Indications from Remote to the 6 Binary Outputs of the SICAM I/O Unit – Server ✧ Parameterize the indications and modes of the binary outputs according to Figure 6-66. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 123
Route the Indications from Remote to the 6 Binary Outputs of the SICAM I/O Unit – Client ✧ Parameterize the indications and modes of the binary outputs according to Figure 6-66. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Route the Indications from Remote to the 6 Binary Outputs of the SICAM I/O Unit – Server ✧ Parameterize the indications and modes of the binary outputs according to Figure 6-66. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 125
Parameterize the messages and modes of the binary outputs according to Figure 6-66. NOTE If you operate several servers in parallel on one client, as shown in Figure 5-2, all servers have to be parame- terized with the same settings. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Use the hardware configuration according to Figure 5-5. NOTE In order to be able to better identify the substation-specific identification of the messages, Siemens recom- mends assigning individual names for the binary input indications. The default names set by the factory can also be kept.
Page 127
6 Operation 6.6 Examples for Parameterization Route 2 Binary Inputs to the 6 Binary Outputs Figure 6-75 Binary Output Settings and Listbox SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 128
6 Operation 6.6 Examples for Parameterization SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Time Synchronization General Internal Time Keeping External Time Synchronization via Ethernet NTP External Time Synchronization via Fieldbus Internal Time Synchronization via RTC SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
DST Status Bit With "1", the DST status bit implemented in the SICAM I/O Unit signals that the local daylight saving time is active. The operational indication "Daylight saving time" is displayed. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
In these cases, SICAM I/O Unit is not synchronized anymore. The device uses the internal clock (on millisec- onds time basis) and the last valid drift. After the programmable delay time, the device reports "Clock Error", see chapter 12. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
NOTE The parameterization of time is described in detail in chapter 6.3.3.5, section Internal Time Synchronization. For information regarding the data format, refer to chapter 8.2.7.1 and chapter 8.2.8.4. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
It is possible to directly connect 2 devices with Ethernet interface due to the integrated Ethernet switch. 8.1.1.1 TCP/IP Protokol Stack SICAM I/O Unit supports the following TCP/IP services: • TCP/IP IPv4 • DHCP Client (Dynamic Host Configuration Protocol) • NTP (Network Time Protocol) • HTTP Server SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 135
If the device is directly connected to a PC (without Ethernet switch), the PC needs a longer period to be able to detect the connection and therefore to receive the ARP telegram. In this case it may not be detected when PC and device have the same IP address. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 136
100BaseT (RJ45), pin assignment according to DIN EN 50173, Automatic patch/crossover cable recognition 100 Ω to 150 Ω STP, CAT5 (shielded twisted-pair cable), max. 100 m if well • Connecting cable: installed SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
• Fiber optical idle state: Light off You can modify these parameters during the parameterization, see chapter 6.3.3.8. The connection is a ST connector BFOC/2.5 for sending and receiving, 820 nm. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 138
8 Communication 8.1 Communication Features Location of the RS485 Interface on the Device RS485 connector Figure 8-3 RS485 Interface of I/O Unit 7XV5673-0JJ10-1AA1 FO interface Figure 8-4 FO Interface of I/O Unit 7XV5673-0JJ20-1AA1 NOTE The pin assignment of the RS485 plug connector is described in chapter 11.1.3.
Combination of writing (request indication) and reading (answer indication) (17H) 4x Registers in one or more holding registers; writing and reading do not have to take place in the same register. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Indication from Remote indication is only controlled via the I/O mirror. Exception-Code 04 SERVER_FAILURE • Error during the time format conversion in the Modbus server because a faulty date/time format was received via Modbus (for example month format > 12). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
10 s 0 s = switch off 1 s to 65 535 s 600 * 100 ms 0 s = none Communication supervision time 100 ms to 6 553 400 ms SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Modbus UDP Port number 51000 10000 to 65535 Access rights Full Full Read only 8 * 10 ms 0 s = invalid Communication supervision time 10 ms to 60 000 ms SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
None, 1 stop bit None, 2 stop bits Full Full Access rights Read only 600 * 100 ms 0 s = none Communication supervision time 100 ms to 6 553 400 ms SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
The register with the lowest address contains the most significant byte (MSB). The register with the highest address contains the least significant byte (LSB). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 145
10H set: Daylight saving time active • 20H set: Date/time error (equivalent to FAIL bit in Table 7-1) NOTE For the time synchronization via Ethernet, Siemens recommends the use of NTP, see chapter 7. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 146
In d ica tio n 1 Holding register 0141 Where: • Q: Status/quality bit: 0 = OK, 1 = invalid • V: Value bit: 0 = OFF, 1 = ON See also chapter 8.2.7.2. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
(string, max. 32 characters) 0025 to 0040 Example: Device name from the configuration “IO_UNIT #1” (string, max. 32 characters) 0041 to 0049 Example: Device serial number “BF0904075879” (string, max. 16 characters) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 148
The time synchronization only takes effect when the time has been completely transmitted. Data type: Date/time Register Type of information Remark 0065 See chapter 8.2.7.1 Milliseconds 0066 Hours/minutes 0067 Month/day 0068 Time status/year SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 149
1 = Check settings 0101/2 Settings Activate 1 = Activate settings 0101/2 Reserved NOTE Registers between 0101 and 0141 that are not shown can be read too during requests and return the value 0. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 150
Relay output 2 at the terminal block P, terminals P3/4 0131/2 Relay output 3, terminal block P Relay output 3 at the terminal block P, terminals P5/6/7 0131/2 Reserved 0131/2 Reserved SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 151
Binary input 2 at the terminal block P, terminals P9/10 0135/2 Binary input 3, terminal block P Binary input 3 at the terminal block P, terminals P11/12 0135/2 Reserved 0135/2 Reserved SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 152
For controlling the relay outputs via the communication 0141/2 Indication 2 from Remote 0141/2 Indication 3 from Remote 0141/2 Indication 4 from Remote 0141/2 Indication 5 from Remote 0141/2 Indication 6 from Remote 0141/2 Reserved 0141/2 Reserved SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
For other user port numbers: ≥ 3 connection attempts via standard port 502 and/or ≥ 3 connection attempts via user port • Access rights: Default: Full • Communication supervision time: Default: 60 000 ms SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 154
Total number of sent bytes to UDP port • Good messages: Total number of received telegrams that were detected as valid Modbus telegrams • Bad messages: Total number of telegram errors SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 155
Total number of bytes sent to the RS485 or FO interface • Framing error: Number of detected frame errors (invalid stop bit, for example if the baud rate is wrong) • Parity error: Number of detected parity errors (wrong parity) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 156
0 • Access rights violations: Total number of write accesses received if the parameter Access rights is set to Read only in the Communication serial input/output window (see chapter 6.3.3.8) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Operating mode I/O mirror client Server IP address 192.168.0.56 Server port 51000 10000 to 65535 Response timeout 3 * 10 ms 0 ms = invalid 10 ms to 60 000 ms SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 158
255.255.255.0 Default gateway 192.168.0.1 Operating mode I/O mirror server Port number 51000 10000 to 65535 Communication supervision time 8 *10 ms 0 ms = invalid 10 ms to 60 000 ms SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Fiber optical idle state Light ON Response Timeout Setting Siemens recommends the response timeout settings indicated in the following table for the respectively param- eterized baud rate in the communication mode bidirectional: Table 8-8 Response Timeout Settings Depending on the Set Baud Rate...
Page 160
Light OFF optical idle state Light ON Communication Supervision Time Siemens recommends the monitoring time communication settings indicated in the following table for the respectively parameterized baud rate: Table 8-10 Monitoring Time Communication Settings Depending on the Set Baud Rate...
Received bytes in the last 10 s • Sent bytes/10 s: Sent bytes in the last 10 s • Bad messages/10 s: Number of frame errors in the last 10 s SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 162
• Bad messages: Total number of telegram errors since the start of the device or since last deleting the counter SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 163
Diagnosis Serial Communication - I/O Mirror Client Parameter • Operating mode: I/O mirror client • Communication mode: Bidirectional • Baud rate: Default: 115 200 bit/s • Response timeout: Default: 30 ms • Send time synchronization: SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 164
Communication mode unidirectional: Always data exchange • Transfer time: Transfer time of a telegram cycle from client to server and back. Communication mode unidirectional: Time between 2 sent broadcast telegrams to server SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 165
Received bytes in the last 10 s • Sent bytes/10 s: Sent bytes in the last 10 s • Bad messages/10 s: Number of telegram errors in the last 10 s SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 166
Startup 1 fail: Incorrect MLFB number Startup 2: Start phase 2 has started Startup 2 fail: Incorrect device configuration values Startup 3: Waiting for “Data Exchange” Data Exchange: Normal data exchange between client and server SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
1 to 6 InClass GGIO InName CTRL/ProxyGGIO1 Data Objects Status information SPCSO1~6 Indications from remote 1 to 6 *) Indications from remote will be routed to binary outputs, refer to chapter 6.3.3.2 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 168
Status of the binary outputs 1 to 6 Table 8-14 Battery inst desc Battery status InClass ZBAT InName CTRL/ZBAT1 Data objekts Status information Battery voltage (not available, invalid) BatLo Battery failure (undervoltage or battery is mis- sing) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
SCSM: IEC 6185-9-2 used SCSM: other Generic substation event model (GSE) Publisher side Subscriber side Transmission of sampled value model (SVC) Publisher side Subscriber side Y = supported; N or empty: not supported SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 171
If GSE (B31/32) is supported GOOSE GSSE If SVC (41/42) is supported Multicast SVC Unicast SVC If Server or Client side (B11/12) supported Time File Transfer Y = supported; N or empty: not supported SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 172
ACSI Service Conformance Statement Services Client Server Comments TP/MC Server ServerDirectory Application association Associate Abort Release Logical device LogicalDeviceDirectory Logical node LogicalNodeDirectory GetAllDataValues Data GetDataValues SetDataValues GetDataDirectory GetDataDefinition Data set GetDataSetValues SetDataSetValues CreateDataSet SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 175
SendUSVMessage GetUSVCBValues SetUSVCBValues Control Select SelectWithValue Cancel Operate Command-Termination TimeActivated-Operate File transfer GetFile SetFile DeleteFile GetFileAttributeValues Time Time resolution of internal clock nearest negative power of (1 ms) 2 in seconds SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 176
T2 (100 μ T3 (25 μ T4 (4 μ T5 (1 Supported TimeStamp resolution nearest negative power of (1 ms) 2 in seconds Y = supported; N or empty: not supported SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
What is the maximum and minimum Max MMS PDU size 20 000 MMS PDU size Min MMS PDU size What is the maximum startup time 45 seconds after a power supply interrupt SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 178
What is the maximum number of data Not restricted; values in one GetDataValues request Depends on the max. MMS PDU size given above. What is the maximum number of data values in one SetDataValues request SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 179
(compare PICS) data change quality change data update general interrogation The supported optional fields are sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference buffer-overflow entryID conf-rev segmentation Can the server send segmented reports SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 180
What quality bits are supported LeapSecondsKnown ClockFailure ClockNotSynchronized Describe the behavior when the time synchro- After a waiting period, time quality is set to nization signal/messages are lost ClockNotSynchronized and ClockFailure SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 181
Mode is equal to SERVER OriginateTimestamp is equal to value sent by the SNTP client as TransmitTimestamp RX/TX timestamp fields are checked for reasonableness SNTP version 3 and/or 4 Other (describe) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 182
Ambiguity in use of trigger tissue.mspx?issueid=332 options http://www.tissues.iec61850.com/ Reporting and BufOvl tissue.mspx?issueid=329 http://www.tissues.iec61850.com/ Write Configuration attribu- tissue.mspx?issueid=322 te of BRCBs http://www.tissues.iec61850.com/ SqNum in Buffered tissue.mspx?issueid=301 Reports http://www.tissues.iec61850.com/ Attribute Resv in BRCB tissue.mspx?issueid=300 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 183
T tissue.mspx?issueid=30 Services Which are Not Supported • Substitution model • Setting group control model • Logging model • Generic substation event model • Control model • File transfer model SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Statuses With IEC 61850, the following statuses are displayed: IEC 61850 Communication status: Status of communication: OK or Fail Port number: Set port number, 102 Information IED Name NO.: Default: 1 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
+10 °C to +35 °C (+50 °F to +95 °F). Siemens furthermore recommends connecting the device to supply voltage once a year for 1 to 2 days in order to form the inserted electrolytic condensers. This procedure should also be carried out before operating the device.
Failures and LED Indications 10.1 General Inspection 10.2 Commissioning during Failures 10.3 Indications Signaled by LEDs 10.4 Troubleshooting and Repair SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Compliance with the access rights according to chapter 4.5 • Compliance with the commissioning sequence of the device according to chapter 4.7 • Evaluation of the LED failure indications, see chapter 10.3. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Figures 10-1 Boot Loader Starting the User Interface without Loading a New/Different Firmware ✧ Click the Run Application button. The following message appears: Figures 10-2 Boot Loader Message of Run Application SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
(LEDs RUN (green) and H1 (yellow) are off). ✧ Release the IP-Addr. button. SICAM I/O Unit starts the Boot Loader with the Boot Loader HTML page (see Figure 10-1). SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
LED flashing: Ethernet link is up and data is transferred LED off: no Ethernet partners connected Table 10-1 Indications Signaled by LEDs Meaning Device switched off ERROR No firmware loaded ERROR SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 192
Boot loader started; no process application exists. ERROR ERROR DHCP active (H1 switches off after reception of the IP address via DHCP) ERROR Default IP address by pressing the IP-Addr. push-button SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 193
LED RUN (green) is lit after the IP address is received by the DHCP server Default IP address is applied by pressing the IP-Addr. push-button. ERROR Double IP address is detected. ERROR ERROR SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Electrostatic sensitive devices (ESD). If you suspect any damage on the device, Siemens recommends sending the entire device to the manufacturer. For this purpose, it is best to use the original transport packaging or similar packaging.
U low ≤ 44 V (at rated voltage 110 V) U high ≥ 176 V Threshold voltage 176 V U low ≤ 88 V (at rated voltage 220 V) Maximum input voltage 300 V SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 197
4.7 nF, ± 20 %, AC 250 V Contact life Expected contact life > 10 , mechanical, at 300 switching cycles/min Expected contact life > 10 , electric (AC), at 20 switching cycles/min (resistive load) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Modbus UDP IEC 61850 Voltage strength DC 700 V Transmission rate 10/100 Mbit/s 100 Ω to 150 Ω STP, CAT5 Cable for 100Base-T Max. cable lenght 100 m, if well installed 100Base-T SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 199
Siemens recommends the use of a bus termination plug with integrated (activatable) resistors in accordance with Figure 11-1, for example plugs with 35°-cable outlet type 6ES7972-0BA42-0XA0 (see chapter 2.2). Use a 2-wired, twisted and shielded cable (see chapter 2.2). In case of outdoor mounting Siemens recommends a SICAM I/O Unit, 7XV5673, Device Manual...
11 Technical Data 11.1 General Device Data rodent protection. You can find current installation material at SIEMENS IS in the "Catalogue for Industrial Communication", chapter "PROFIBUS", see also: http://www.automation.siemens.com/mcms/automation/en/industrial-communications/Pages/Default.aspx. The 9 pin D-sub socket of the RS485 interface is connected as follows: Pin No.
(except for communication 1.2 µs/50 µs; 0.5 J; ports) and against the PE terminal of class III 3 positive and 3 negative impulses at intervals of 1 s SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 202
Radio noise voltage to lines, only auxiliary voltage 150 kHz to 30 MHz Limit Class B IEC-CISPR 11 Interference field strength 30 MHz to 1000 MHz Limit Class B IEC-CISPR 11 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
3 shocks (in both directions of the 3 axes) Continuous Shock Semi-sinusoidal IEC 60255-21-2, Class 1; 10 g acceleration, duration 16 ms, IEC 60068-2-29 test Eb each 1000 shocks (in both directions of the 3 axes) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
56 days of the year up to 93 % relative humidity; condensation must be avoided! Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor subject to large fluctuations in temperature that may cause condensation to occur.
96 mm x 96 mm x 100 mm 3.78 inch x 3.78 inch x 3.94 inch 111.3 (4.38) 103.8 (4.09) Dimensions in mm (inch) Figure 11-2 Dimensional Drawing of the I/O Unit 7XV5673 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 206
11 Technical Data 11.3 Dimensions SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Indication off: After setting the clock via HTML (see chapter 6.3.3.5) During battery failure at device startup Time Set The time was set. Indication on: Time set Only when setting the clock via HTML SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 208
Indication off: No serial message was received during the set monitoring time. See chapter 6.3.3.8 Settings Load Starting to change the Indication on: Start of changes parameters of the passive Indication off: Changes complete parameter set. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 209
ON: At least one valid Modbus UDP telegram was received (which does not lead to a Modbus Exception Response.) OFF: No Modbus UDP telegram was received within the set monitoring time. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 210
ON: At least one valid Modbus RTU telegram was received (this does not lead to a Modbus Exception Response.) OFF: No Modbus RTU telegram was received within the set monitoring time. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 211
I/O serial co- (Serial I/O mirror mmunication, including the (server or bidirectional client)) counter for faulty telegrams, which are used for the analysis of I/O Serial Fail > 0.05 %. SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
NOTE for user on the online help This chapter is integrated as an online help in the user interface. The description of parameterization of the operating parameters can be found in the manual I/O Unit 7XV5673, order number E50417-H1040-C484-A3. SICAM I/O Unit, 7XV5673, Device Manual...
I/O Mirror OK Invert source (can be set individually for all relay outputs) Operating mode Persistent Persistent (can be set individually for all relay outputs) Persistent with fail safe Pulse Pulse with retrigger SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Binary In 2 - Terminal block P Binary In 3 - Terminal block P I/O Ethernet OK I/O Ethernet Fail > 0.05 % I/O Serial OK I/O Serial Fail > 0.05 % I/O Mirror OK Indication inverted SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
0:00 to 23:00 (full hour) End of DST October January to December Last week First week Second week Third week Fourth week Last week Sunday Sunday to Saturday 03:00 AM 0:00 to 23:00 (full hour) SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
10 ms to 60 000 ms I/O Mirror Client (can only be parameterized, if no I/O mirror mode is selected under Serial Communication) Server IP address 192.168.0.56 Server port 51000 10000 to 65535 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 219
0 s = invalid 10 ms to 60 000 ms (Settings recommended by Siemens see chapter 8.3.2.2) If there is an FO interface: Light OFF Light OFF Fiber optical idle state Light ON SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
DD-MM-YYYY, Time with 12 h AM/PM MM/DD/YYYY, Time with 24 hours MM/DD/YYYY, Time with 12 h AM/PM Activation password 000000 Any 6 to 14 characters Maintenance password 311299 Any 6 to 14 characters SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Firmware: Program code for execution in a microcontroller Gateway Enables networks based on different protocols to communicate with each other. Holding register Area for representing data in Modbus communication HTML Hypertext Markup Language; application in World Wide Web SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 222
Time the output needs to react to a signal change at the device input. Time measured from an instant change at the AC input until the corresponding change of a DC output quantity has reached 90% of its final value. RJ45 Ethernet plug connector SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 223
Transmission Control Protocol/Internet Protocol: Family of network protocols UDP/IP User Datagram Protocol/Internet Protocol: Family of network protocols Universal Time Coordinated: Universal time standard referred to the time at the prime meridian SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...
Page 226
Time synchronization 12, 77, 131 Time synchronization via ethernet NTP 79 Time synchronization via fieldbus (modbus) 79 Transport 186 Troubleshooting 194 Unidirectional binary signal transmission 39 User information 11 Value view 103 Working examples 37 SICAM I/O Unit, 7XV5673, Device Manual E50417-H1040-C484-A3, Edition 05.2012...