6.3.3.8 Serial Communication
Table 6-10
Parameter
Bus protocol/Operating mode
Device address
Baud rate
Parity
Access rights
Communication supervision time
If there is an FO interface:
Fiber optical idle state
(can be parameterized, if no I/O mirror mode is selected under Communication Ethernet)
Communication mode
Baud rate
Response timeout
(only in communication mode bidi-
rectional)
Send time synchronization
If there is an FO interface:
Fiber optical idle state
(can be parameterized, if no I/O mirror mode is selected under Communication Ethernet)
Baud rate
Communication supervision time
If there is an FO interface:
Fiber optical idle state
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Serial Communication Settings
Modbus RTU
1
19 200 bit/s
Even
Full
600 * 100 ms
Light OFF
Bidirectional
115 200 bit/s
3 * 10 ms
no
Light OFF
115 200 bit/s
8 * 10 ms
Light OFF
Default Settings
-None-
Modbus RTU
I/O Mirror client
I/O Mirror server
Modbus RTU
1 to 247
Acc. to list box
(see chapter 13.2.4)
Acc. to list box
(see chapter 13.2.4)
Full
Read only
0 s = none
100 ms to 6 553 400 ms
Light OFF
Light ON
I/O Mirror Client
Bidirectional
Unidirectional
Acc. to list box
(see chapter 13.2.4)
10 ms bis 60 000 ms
(Siemens recommendation,
see chapter 8.3.2.1)
yes
no
Light OFF
Light ON
I/O Mirror Server
Acc. to list box
(see chapter 13.2.4)
0 s = invalid
10 ms to 60 000 ms
(Siemens recommendation,
see chapter 8.3.2.2)
Light OFF
Light ON
6 Operation
6.3 Configuration of the Device
Settings
97