Serial Communication - Siemens 7XV5673 Device Manual

Sicam i/o unit
Hide thumbs Also See for 7XV5673:
Table of Contents

Advertisement

13 Operating Parameters
13.2 Administrative
Response timeout
(can only be parameterized, if no I/O mirror mode is selected under Serial Communication)
Port number
Communication supervision time
IEC 61850 Edition
IED name number
Multicast MAC address
4)
App ID
4)
VLAN ID
VLAN priority
Retransmit MIN
Retransmit MAX
1) After the parameter changes have been enabled, the device resets.
2) After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
3) After having selected IEC 61850 or changed the IEC 61850 settings, the device must be restarted.
4) The parameters stated here are only used when yes is selected for "Use settings in the table below" (see
Bild 6-36 ). This allows for a simple configuration of the GOOSE publishers without using DIGSI and the
SICAM I/O Mapping Tool.
13.2.4

Serial Communication

Parameter
Bus protocol/Operating mode
Device address
Baud rate
218
Bus Protocol IEC 61850
4)
4)
4)
4)
4)
Modbus RTU
1
19 200 bit/s
3 * 10 ms
I/O Mirror Server
51000
8 * 10 ms
3)
Edition 1
1
4
5
3000
Default setting
-none-
Modbus RTU
I/O Mirror client
I/O Mirror server
Modbus RTU
1 to 247
1200 bit/s
2400 bit/s
4800 bit/s
9600 bit/s
19 200 bit/s
38 400 bit/s
57 600 bit/s
115 200 bit/s
0 ms = invalid
10 ms to 60 000 ms
10000 to 65535
0 ms = invalid
10 ms bis 60 000 ms
Edition 1
Edition 2
0 to 65534
[xx-xx-xx-xx-xx-xx] hexadecimal
[xxxx] hexadecimal
[xxx] hexadecimal
0 to 7
1 ms to 500 ms
500 ms to 65 534 ms
Settings
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012