To change the Ethernet communication, proceed as follows:
In the navigation window, select the Operational menu, then the Administrative submenu and click
Communication Ethernet.
The Communication Ethernet input/output window opens.
Figure 6-32
Enter the IP address into the IP address field.
Enter the subnet mask into the Subnet mask field.
Enter the gateway into the Default gateway field.
NOTE
When the network settings have been changed and the changed parameters have been activated (see descrip-
tion below), the device automatically perform a restart.
If you want to switch on the Ethernet switch, select the option yes in the option field Ethernet switch on.
NOTE
The Ethernet switch is switched off at delivery to ensure a correct operation of the I/O mirror of 2 devices without
Y-cable. Only switch on the Ethernet switch (option yes), if you connect a Y-cable at the Ethernet connector.
Select the desired Bus protocol, the desired Operating mode or -none- from the Bus protocol/
Operating mode list box.
If you select -none-, there will be no log and no mode available. In this case, click the Send button. If you
have selected a Modbus protocol or an Operating mode, parameterize as follows:
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Configure Tab, Communication Ethernet via Modbus TCP Input/Output Window
6 Operation
6.3 Configuration of the Device
83