To change the Ethernet communication, proceed as follows:
✧
In the navigation window, select the Operational menu, then the Administrative submenu and click
Communication Ethernet.
The Communication Ethernet input/output window opens.
Figure 6-32
✧
Enter the IP address into the IP address field.
✧
Enter the subnet mask into the Subnet mask field.
✧
Enter the gateway into the Default gateway field.
NOTE
When the network settings have been changed and the changed parameters have been activated (see descrip-
tion below), the device automatically perform a restart.
✧
If you want to switch on the Ethernet switch, select the option yes in the option field Ethernet switch on.
NOTE
The Ethernet switch is switched off at delivery to ensure a correct operation of the I/O mirror of 2 devices without
Y-cable. Only switch on the Ethernet switch (option yes), if you connect a Y-cable at the Ethernet connector.
✧
Select the desired Bus protocol, the desired Operating mode or -none- from the Bus protocol/
Operating mode list box.
If you select -none-, there will be no log and no mode available. In this case, click the Send button. If you
have selected a Modbus protocol or an Operating mode, parameterize as follows:
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Configure Tab, Communication Ethernet via Modbus TCP Input/Output Window
6 Operation
6.3 Configuration of the Device
83