Siemens 7XV5673 Device Manual page 94

Sicam i/o unit
Hide thumbs Also See for 7XV5673:
Table of Contents

Advertisement

6 Operation
6.3 Configuration of the Device
Configuration Using DIGSI 4
NOTE
Using DIGSI 4 is the easiest way to perform the GOOSE Subscriber configuration.
IEC 61850 Edition 2 requires DIGSI 4.86 or higher.
The handling of DIGSI 4 is assumed and not described in this manual.
If you do not have DIGSI 4.86 or higher at your disposal, perform the installation as described in Manual Con-
figuration Without DIGSI 4.
The following steps must be executed for configuring the IEC 61850 GOOSE Subscribers:
Download the ICD file from the device.
Import the ICD file into DIGSI 4 (as other IEC 61850 communicator).
Change the IED name via the object properties (IED name S_IO_xxxxx, the name must conform to this
pattern).
Open the station for interconnecting GOOSE (see DIGSI 4 manual).
NOTE
DIGSI 4 allows the interconnection of binary signals to the DOs (data objects) SPCSO1 to SPCSO6 in LN
ProxyGGIO1.
It is not possible to interconnect external GOOSE messages to other objects in the SICAM I/O Unit.
SPCSO1 to SPCSO6 correspond to the indications Indication 1 from Remote to Indication 6 from Remote
in the SICAM I/O Unit (see chapter 6.3.3.2).
After having exported the SCD file, open the SICAM I/O Mapping Tool program.
Enter the same IED name as in DIGSI 4 in the SICAM I/O Mapping Tool (e.g. IED name S_IO_00002, see
Figure 6-42).
Figure 6-42
Click Load in the menu bar and load the SCD file into the SICAM I/O Mapping Tool. A validation is
performed.
94
SICAM I/O Mapping Tool
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents