8 Communication
8.2 Modbus
8.2.2

Exception Responses

NOTE
The exception responses for Modbus TCP and Modbus UDP (Ethernet) and Modbus RTU (serial) are the
same.
The Modbus server performs a series of consistency checks of the Modbus client requests, and if errors (for
example request to read a nonexistent register) are detected, it generates Modbus exception codes which are
signaled to the Modbus client in exception responses messages.
The messages contain the following codes:
Exception-Code 01
ILLEGAL_FUNCTION
The Modbus client uses a function that is not supported by the Modbus server of the SICAM I/O Unit (the
supported Modbus functions are listed in chapter 8.2.1).
Exception-Code 02
ILLEGAL_DATA_ADDRESS
An attempt is made to read out or write to a nonexistent Modbus register (see chapter 8.2.8, Modbus
mapping for valid registers).
An attempt is made to read out or write to too many registers. A Modbus message enables reading out
125 holding registers and writing to 123 holding registers maximum.
The Modbus clients tries to write to a register in the Modbus server for which only read access is allowed
according to the Modbus mapping (see chapter 8.2.8).
Exception-Code 03
ILLEGAL_DATA_VALUE
The Modbus client addresses a register, for which the access to partial data was not released.
The Modbus client attempts to write to the Modbus server for which the access rights are set to "read only".
The Modbus client, the I/O mirror server, or the I/O mirror client (Ethernet or serial) tries to control the
writing of the Indication from Remote indication into the register of the SICAM I/O Unit. If the SICAM I/
O Unit is configured as I/O mirror server or I/O mirror client (apart from I/O mirror server, serial, unidirec-
tional), the Indication from Remote indication is only controlled via the I/O mirror.
Exception-Code 04
SERVER_FAILURE
Error during the time format conversion in the Modbus server because a faulty date/time format was
received via Modbus (for example month format > 12).