Siemens 7XV5673 Device Manual page 121

Sicam i/o unit
Hide thumbs Also See for 7XV5673:
Table of Contents

Advertisement

Setting of the SICAM I/O Unit – Client with Ethernet Communication in I/O Mirror Client Mode
Figure 6-69
Setting of 6 Binary Inputs of the SICAM I/O Unit – Client
Parameterize the threshold value voltages of the binary inputs according to Figure 6-65.
Route the Indications from Remote to the 6 Binary Outputs of the SICAM I/O Unit – Client
Parameterize the messages and modes of the binary outputs according to Figure 6-66.
NOTE
Please note, that when parameterizing the SICAM I/O Unit – client, its IP address has to differ from the Server
IP address of the SICAM I/O Unit – server. If necessary, change the IP address of the SICAM I/O Unit – client.
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Setting of the Ethernet Communication for I/O Mirror Client
6 Operation
6.6 Examples for Parameterization
121