6 Operation
6.3 Configuration of the Device
Select the Source of the message from the Indication list box. You can select the following messages:
Ready and status indications, for example Device OK, Modbus TCP OK
Indications about present device activities, for example Settings load
Error indications, for example Battery Failure, Ethernet Link Error
Administrative indications, for example Daylight Saving Time
Communication indications, for example Indication 1 from Remote
Indications to the binary inputs, for example Binary input 1 - Terminal block 1
Select -none- to disable the binary output.
In the Source inverted section select whether you want to invert the indication for the output (yes) or not
(no).
Select the output mode at the binary outputs in the Operating mode list box. The following output types
are available:
Persistent: The binary output has the status ON or OFF. If the indication becomes invalid, the binary
output continues to maintain its current status.
Indication
Binary output
not inverted
Binary output
inverted
Figure 6-24
Fail-safe persistent output: If the message becomes invalid and Source inverted = no has been
parameterized, the binary output switches to OFF mode. If the message becomes invalid and Source
inverted = yes has been parameterized, the binary output switches to ON mode.
Indication
Binary output
not inverted
Binary output
inverted
Figure 6-25
72
Indication
ON
OFF
Output
ON
OFF
ON
Output
OFF
Persistent
Indication
ON
OFF
Output
ON
OFF
ON
Output
OFF
Persistent with Fail Save
invalid
invalid
invalid
invalid
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012