Remote Modbus/Tcp Device Configuration - Comtrol DeviceMaster EtherNet/IP-Modbus EIP-MOD User Manual

Table of Contents

Advertisement

Remote Modbus/TCP Device Configuration

5.4. Remote Modbus/TCP Device Configuration
All Modbus devices not configured remotely are assumed to be local, or connected to this gateway. The
location of all local Modbus devices is determined automatically.
1. Access the Remote Modbus/TCP Device Configuration page by clicking Modbus | Remote Modbus
Configuration.
2. Click the Add Remote Configuration button to add additional remote devices.
The following table provides details about configuration options.
Device ID #
Remote IP Address
Remote Modbus/TCP
Port (Default = 502)
Timeout (ms)
(Default = 1000
msec)
Dedicated
Connection (Default
= Off)
Send Writes First
(Default = Off)
DeviceMaster EIP-MOD User Guide: 2000664 Rev. A
Remote Modbus/TCP Device Configuration Page
The Device ID (also often called the unit ID) of the remote device must be
unique. The Device ID range is 1-255. 0 means that it is not configured.
IP address of the Modbus/TCP device. All 0s means that it is not configured.
Note: The IP address of the DeviceMaster EIP-MOD will not be accepted as
valid configuration data.
The TCP/IP port (1-65535) to connect to on the remote device.
The maximum allowable time (0 to 65535 msec) for a slave device to respond to
a message before the message is considered timed out.
If selected, a dedicated Modbus/TCP connection will be used to connect to this
remote device.
Note: This is most commonly used when connecting to another gateway,
multiple devices are being accessed, and maximum bandwidth is desired.
If selected, will forward write messages before forwarding any pending read
messages.
Note: This is most commonly used when multiple messages may be outstanding
for the remote device(s) and low latency for write messages is desired.
Chapter 5. Modbus Menus- 57

Advertisement

Table of Contents
loading

Table of Contents