Ethernet/IP Interface Statistics Page
Broadcasts Messages
Received
Class 3 Messages/
Responses Transmitted
Class 1 Output Updates
(From PLC)
Class 1 Input Updates
(To PLC)
Client Objects Requests Displays the number of Class3 request messages received from the PLC(s).
Good Responses From
PLC
Bad Responses From
PLC
No Responses From PLC
Invalid Network Paths
Pending Request Limit
Reached
Unexpected Events
Unsupported CIP Class
Errors
Unsupported CIP
Instance Errors
Unsupported CIP
Service Errors
Unsupported CIP
Attribute Errors
Improper Configuration
Errors
112 - Chapter 8. Diagnostic Menus
EtherNet/IP Interface Statistics Page (Continued)
Displays the number of broadcast messages received from the PLC(s).
Displays the number of messages and responses sent to the PLC(s).
The number of Class 1 output data updates received from the PLC or PLCs.
The number of Class 1 input data updates sent to the PLC or PLCs.
The number of good responses received from the PLC.
Displays the number of bad responses from messages sent to the PLC(s). Bad
responses are typically returned for such errors as:
Incorrect tag or file names
Incorrect tag or file data types
Incorrect tag or file data sizes
PLC is overloaded and cannot handle the amount of Ethernet traffic
PLC malfunction
Displays the number of no responses from messages sent to the PLC(s). No
responses are typically returned for such errors as:
Incorrect IP address
Incorrect PLC configuration
PLC malfunction
PLC is overloaded and cannot handle the amount of Ethernet traffic
Displays the number of network path errors on messages sent to the PLC(s).
These are typically caused by incorrect IP address settings.
Displays the number of pending request limit errors. These errors occur when
the PLC is sending a continuous stream of messages to the DeviceMaster EIP-
MOD faster than the DeviceMaster EIP-MOD can process them.
Displays the number of unexpected event errors. Unexpected event errors occur
when the DeviceMaster EIP-MOD receives an unexpected message from the
PLC such as an unexpected response or unknown message.
Displays the number of unsupported CIP request instance errors. These errors
occur when a message with an invalid class is sent to the DeviceMaster EIP-
MOD.
Displays the number of unsupported CIP request instance errors. These errors
occur when a message with an invalid instance is sent to the DeviceMaster
EIP-MOD.
Displays the number of unsupported CIP request instance errors. These errors
occur when a message with an invalid service is sent to the DeviceMaster EIP-
MOD.
Displays the number of unsupported CIP request instance errors. These errors
occur when a message with an invalid attribute is sent to the DeviceMaster
EIP-MOD.
Displays the number of improper configuration errors. These errors occur when
the DeviceMaster EIP-MOD receives a message that cannot be performed due
to an invalid configuration.
DeviceMaster EIP-MOD User Guide: 2000664 Rev. A