Modbus to EtherNet/IP Tag/File Diagnostics Page
Modbus to EtherNet/IP Tag/File Diagnostics Page (Continued)
No Path
Unexpected Responses
PLC Type
IP Address
Tag/File
Tx Messages
Rx Messages
Error Responses
Reset Statistics
Error Responses
Unexpected Responses
PLC Type
IP Address
Tag/File
Tx Messages
Rx Messages
Error Responses
Reset Statistics
114 - Chapter 8. Diagnostic Menus
Displays the number of no path conditions. No path conditions occur when any
of the following occur:
There is no valid destination to send the Modbus message.
-
There are no serial ports configured as slave ports.
-
There is no remote Modbus configuration for the device ID.
If there is a remote Modbus configuration, the gateway is unable to connect
to the Modbus/TCP IP address.
Displays the number of unexpected read responses received from the Shared
Memory or Modbus device. These occur when an incorrect function code is
received in the response, or a response message is received when it is not
expected.
Displays the EtherNet/IP PLC type that is being written to.
Displays the IP address of the EtherNet/IP PLC in xxx.xxx.xxx.xxx format.
Displays the EtherNet/IP PLC tag or file name.
Displays the number of write messages transmitted to the EtherNet/IP PLC.
Displays the number of valid write responses received from the EtherNet/IP
PLC.
Displays the number of write response errors received from the EtherNet/IP
PLC.
If click it resets the statistics to all zeros.
Displays the number of read response errors received from the Shared Memory
or Modbus device.
Displays the number of unexpected read responses received from the Shared
Memory or Modbus device. These occur when an incorrect function code is
received in the response, or a response message is received when it is not
expected.
Displays the EtherNet/IP PLC type that is being written to.
Displays the IP address of the EtherNet/IP PLC in xxx.xxx.xxx.xxx format.
Displays the EtherNet/IP PLC tag or file name.
Displays the number of write messages transmitted to the EtherNet/IP PLC.
Displays the number of valid write responses received from the EtherNet/IP
PLC.
Displays the number of write response errors received from the EtherNet/IP
PLC.
If click it resets the statistics to all zeros.
DeviceMaster EIP-MOD User Guide: 2000664 Rev. A