Comtrol DeviceMaster EtherNet/IP-Modbus EIP-MOD User Manual page 32

Table of Contents

Advertisement

| Informational Objects | TCP Object (F5 Hex - 1 Instance) | Instance Attributes |
Attribute
Name
ID
Physical Link Object
Structure of:
Path Size
4
Path
Interface Configuration
Structure of:
IP Address
Network Mask
5
Gateway Address
Name Server
Name Server 2
Domain Name
Length Domain Name
Host Name
Structure of:
6
Host Name Length
Host Name
TTL (Time-to-Live) value
8
for IP multicast packets
IP Multicast Address
9
Configuration
Encapsulation Inactivity
13
Timeout
32 - Chapter 2. EtherNet/IP Interface Profile (ControlLogix)
Data Type
UINT
2
Array of USINT
[0]=20 hex
[1]=F6 hex
[2]=24 hex
[3]=01 hex
UDINT
<IP address>
UDINT
<Network mask>
UDINT
<Gateway Addr>
UDINT
<Name server>
UDINT
<Name server 2>
UINT
<Length of name>
STRING
<Domain name>
UINT
0 to 15
STRING
<Default = IP address>
1 to 255
USINT
<Default = 1>
Struct of:
USINT –Allocation
Allocation Control
0=Default Algorithm
Control
1 = Configuration
USINT – Reserved
Num Multicast Addresses:
UINT – Num Mcast
1-32
Start Multicast Address:
UDINT – Start
239.192.1.0 to
Multicast Address
239.255.255.255
Number of seconds of inactivity
USINT
before TCP connection or DTLS
session is closed
Data Value(s)
DeviceMaster EIP-MOD User Guide: 2000664 Rev. A
Access
Rule
Get
Set
Set
Set
Set
Set

Advertisement

Table of Contents
loading

Table of Contents