Modbus to EtherNet/IP Tag/File Configuration Page
Modbus to EtherNet/IP Tag/File Configuration Page (Continued)
PLC Type
(Default = ControlLogix)
IP Address
(Default = 0.0.0.0)
Slot (0-n)
(Default = 0)
Data Type
(Default = INT)
Tag/File
(Default = Blank)
Save
Delete
Delete All
Add Default
Configuration
Clone Line
Sort By
(Read Device ID)
(Default = Disabled)
Sort By
(IP Address)
(Default = Disabled)
DeviceMaster EIP-MOD User Guide: 2000664 Rev. A
Specifies the PLC type to write to:
ControlLogix – This selection enables the full CIP supported interfaces that
provide CIP table read/write capabilities. The ControlLogix PLC family of
PLCs includes the Rockwell ControlLogix, FlexLogix, SoftLogix and other
advanced PLCs. This selection also supports numerous PLCs manufactured
by other manufacturers.
MicroLogix – This selection provides support for Rockwell MicroLogix, SLC
and PLC-5 PLCs. These PLCs only support a limited EtherNet/IP interface
that does not include CIP table read/write support. Only Write-to-File and
Read-from-File communication that use PCCC MSG instructions is
provided.
Enter the IP address of the EtherNet/IP PLC in xxx.xxx.xxx.xxx format.
Enter the slot number of the PLC controller board. This is only required for
chassis type PLCs such as ControlLogix. For all other PLCs, set this value to 0.
The data type of the Tag or File to write to.
SINT – otherwise called 8 bit, or byte sized data
DINT – otherwise called 16 bit, or WORD format
BOOL – a single Boolean value
BIT ARRAY – an array of Boolean values
FLOAT – floating point, otherwise called REAL
Specifies the EtherNet/IP PLC tag or file name. It indicates where to write the
data read from the Modbus device or Shared Memory. This entry supports
ASCII strings containing up to 40 characters.
File names for the PLC-5/ SLC PLCs must be in a SLC/PLC-5 file format (i.e.
N10:0, B20:0/6, etc).
When this button is clicked:
The settings are verified.
Any changes are saved.
The Data Mapping process is immediately reconfigured and begins
performing the configured operations.
Enable the line or lines that you want to delete and click the Save button.
Enable the Delete All option and click the Save button to remove all entries.
Adds a default entry to the end of the list. The entry will not become active
until it is saved by clicking Save.
Adds a new configuration entry to the end of the list that is identical to the
entered line number. The entry will not become active until it is saved by
clicking Save.
Note: No action is taken if the entered line number is invalid.
Reorders the list based on the Read Device ID when Save is selected.
Reorders the list based on the EtherNet/IP PLC IP address when Save is
selected.
Chapter 7. Data Mapping Menus - 71