Vendor Specific Read/Write Holding Registers (73 Hex); Informational Objects; Identity Object (01 Hex, 1 Instance); Class Attributes - Comtrol DeviceMaster EtherNet/IP-Modbus EIP-MOD User Manual

Table of Contents

Advertisement

| Informational Objects | Identity Object (01 Hex, 1 Instance) | Class Attributes |

2.1.4.0.11. Vendor Specific Read/Write Holding Registers (73 Hex)

This service performs first write and then read operations on multiple holding registers in the Modbus
Holding Registers table. This service results in the DeviceMaster EtherNet/IP-Modbus gateway issuing a
Read/Write Holding Registers function (function code 0x17) to either the Shared Memory or the Modbus
Message Routing subsystem. Refer to MODBUS Application Protocol Specification V1.1b3.pdf at
www.modbus.org
for more details.
Note: In order to use this service, the Enable Vendor Specific Modbus Object Services option on the EtherNet/
IP Stack Configuration web page must be selected.

2.2. Informational Objects

The following object definitions are included for informational purposes only. While some software packages,
such as RSLinx make use of these objects, few PLC programmers will have a need to directly access them.

2.2.1. Identity Object (01 Hex, 1 Instance)

The Identity Object provides identification of and general information about the DeviceMaster EIP-MOD.

2.2.1.1. Class Attributes

The following table provides information about the Identity Object (01 hex, 1 Instance) Class Attributes.
Attribute ID
1
Revision
2
Max Class
3
Max Instance
6
Maximum Number Class Attribute
7
Maximum Number Instance Attribute

2.2.1.2. Instance Attributes

The following table provides information about the Identity Object (01 hex, 1 Instance) Instance Attributes.
Attribute ID
1
Vendor ID
2
Device Type
3
Product Code
Revision (product or software release)
Structure of:
4
Major Revision USINT
Minor Revision USINT
5
Status
6
Serial Number UDINT
24 - Chapter 2. EtherNet/IP Interface Profile (ControlLogix)
Name
Name
Data Type
UINT
UINT
UINT
WORD
Data Type Data Value(s) Access Rule
UINT
1
UINT
1
UINT
1
UINT
7
UINT
7
Data Value(s)
909 (Pepperl+Fuchs Comtrol, Inc.)
43 (Generic product device)
As defined by Pepperl+Fuchs
Comtrol, Inc.
1 to 127
1 to 999
See below.
1-FFFFFFFF hex
DeviceMaster EIP-MOD User Guide: 2000664 Rev. A
Get
Get
Get
Get
Get
Access Rule
Get
Get
Get
Get
Get
Get

Advertisement