Execution order and feedback loops

It is possible to draw multi-layer configuration logic that contains feedback loops with the
Application Configuration tool. The execution order of logic functions is calculated
automatically in the Application Configuration tool, but the execution order can also be
set manually. If the automatically calculated value causes the function to be executed one
task cycle time after the other logic functions in the same loop, the execution order number
can be set manually to prevent delays, for example, in output activation.
To perceive accurate time stamps from binary input signals to function
blocks, direct logic connection should be used in the Application
Configuration tool. Due to internal execution order, time stamps may not