ABB RELION 615 Series Engineering Manual page 151

Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC108982-MB E
615 series ANSI
Engineering Manual
Click Don't import IEDs of unknown type to protect the existing IEDs in
case the SCD file does not match the original configuration in PCM600.
Click Replace unknown if it is known that the file includes additional IEDs
that are needed. The IED of type "Generic IEC 61850 IED" is used to integrate
these kinds of IEDs into the plant structure, for example.
Click Ignore PCM Object Type to update the IED object(s) in PCM600 from
the IED type(s) in the SCD file, whether or not the IED type(s) in the SCD file
matches the IED object(s) in PCM600. This option can be used, for example,
when third party IEDs are included in the system and the SCD file sends
GOOSE messages to ABB IEDs included in the project.
Click Ignore Substation Section to not import the SSD file part of the SCD
file.
5.
Click Import when the file definition has been completed.
A progress view displays the importing procedure.
6.
Make connections from the sending IEDs to the receiving function blocks with the
Signal Matrix tool.
Make connections between the signals that the server is sending and the function
blocks on the receiver's side.
7.
Write the configuration to the IED.
In the Plant Structure view, select the IED, right-click and select Write to IED.
IEC 61850 communication engineering
Section 7
143