Section 7
IEC 61850 communication engineering
7.3.2
[1] Applicable when using IET600
140

Engineering vertical and horizontal communication

For IEC 61850 engineering a separate system configuration tool is needed to be used with
PCM600. In PCM600 Ver.2.3 or earlier the recommended tool is CCT600. In PCM600
Ver.2.4 or later the recommended tool is IET600, which is also included in the PCM600
Engineering Pro installation package.In PCM600 Ver.2.5 or later the recommended tool
for smaller projects is the IEC 61850 Configuration tool. For larger projects it is
recommended to use IET600, which is available as a standalone tool.
1.
Create a project in IET600.
2.
Import the SCD file created by PCM600.
3.
Conduct vertical communication engineering (monitoring direction).
3.1. Check the default data sets.
3.2. Configure and/or reconfigure the default data sets.
3.3. Configure additional Report Control Blocks when needed for each data set
used for vertical communication.
3.4. Link the IED clients to the Report Control Blocks.
4.
Conduct horizontal communication engineering.
4.1. Configure GOOSE control blocks for each data set configured for GOOSE
messages.
[1]
[1]
Data sets meant for vertical reporting can only contain data on
the data object level, not on the data attribute level.
The data set for GOOSE can contain signals on the data
attribute or data object level. Data object level GOOSE entries
can only be received of the following CDC types: SPS, SPC,
ACD, ACT, DPS, DPC, INC, INS, ENC and ENS.
Up to five report clients can be configured.
1MAC108982-MB E