Section 3
PCM600 tool
3.3
30
GUID-B3D2C177-2737-425F-B4E4-22F4D4326343-ANSI V2 EN
Figure 8:
Selecting the connectivity package versions
PCM600 recognizes the installed connectivity packages during start-up, and the
corresponding IED types are available in PCM600 when starting a new project.
The 2.0, 4.0, 4.2 and 5.0 FP1 ANSI protection relay versions can be in the
same PCM600 project only if the project was created with ANSI 4.2
connectivity package.

PCM600 projects

A typical project in PCM600 contains a plant structure including one or several IED
objects, where each IED object contains the engineering data created or modified using
the different PCM600 tools.
Several projects can be created and managed by PCM600, but only one project can be
active at a time.
Regardless the protocol used in installation for each project, the IEC 61850 version must
be selected when adding the first IED to plant structure. After the initial selection, all IEDs
in plant structure use the selected version, either Edition 1 or Edition 2. In case the IEC
61850 is not used for station bus, the default version can be applied. By default, the IEC
1MAC108982-MB E