1MAC108982-MB E
Section 2
615 series ANSI
Engineering Manual
Relay engineering process
PCM600 is used for various tasks in the protection relay engineering process.
Relay engineering management
Organizing the bay protection relays in the structure of the substation by
defining voltage levels and bays below the substation. PCM600 manages the
project.
Configuring the protection relay functions (for example, protection and control
functions) by using the Application Configuration tool.
Configuring the parameters and setting values for the protection relay itself and
for the process functions by using the Parameter Setting tool.
Drawing single-line diagrams and making links to dynamic process values by
using Graphical Display Editor. The single-line diagrams are displayed in
LHMI and WHMI on the bay protection relay.
Configuring connections between the application configuration function
blocks and physical hardware inputs and outputs by using the Signal Matrix
tool or the Application Configuration tool.
Configuring the events shown on the LHMI using the HMI Event Filtering tool.
Communication management
IEC 61850 station communication engineering is done with a separate tool, for
example, CCT600 or IET600. PCM600 interacts with CCT600 or IET600 by
importing and exporting SCL files.
Configuring the GOOSE receiving data connections to the protection relay's
application configuration function blocks by using the Application
Configuration tool and the Signal Matrix tool.
Configuring protocol data mapping for Modbus or DNP3 with the
Communication Management tool.
Configuring the sampled values (process bus) between the devices using the
Application Configuration tool and IEC 61850 Configuration tool.
Record management
Relay engineering process
Section 2
15