Standard Configuration Concept - ABB RELION 615 Series Engineering Manual

Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC108982-MB E
2.2
615 series ANSI
Engineering Manual
Project
Substation = name of the substation
Voltage level = identifies to which grid type or part the device belongs in the
substation
Bay = bay within the voltage level
IED = the selection of the IED that is used in the bay; it is possible to insert several
IEDs within a bay, for example, one control device and two protection relays

Standard configuration concept

The product series covers protection relays developed for the protection of medium
voltage applications. Every product has predefined application-specific software called
standard configuration that contains protection, control, supervision and measurement
function blocks and default logical connections; for more information, see the application
manuals. The product also includes the standard configuration specific default single-line
diagram.
The standard configuration software consists of connections between an application's
functions developed according to the needs of a particular functional application. The
inputs and outputs are similarly assigned to a default set of connections such as position
indication and Master trip. The alarm LEDs are assigned to default connections based on
the order number.
Current and voltage channels for protection and measurement functions
are fixed as a part of standard configuration and cannot be reassigned with
Signal Matrix or Application Configuration in PCM600.
The single-line diagram consists of an application-specific general arrangement of a
single-line diagram that includes position indications and the selection of controllable
objects and measurements.
The content of the standard configuration depends on the intended functional application.
The standard configurations also have selectable software options, which are selected
when ordering the protection relay. Some of the software options are related to the
protection relay hardware.
The standard configurations can be used as is, but they can also be modified by using the
PCM600. The standard configuration itself can be modified or extended by using the
Application Configuration tool, the Signal Matrix tool and the communication
configuration tools. The single-line diagram can also be modified with Graphical Display
Editor.
Relay engineering process
Section 2
19