Section 4
Setting up a project
4.6
70
GUID-6F47B4AD-B956-4F77-A6A2-DE6F4A71D607 V2 EN
Figure 42:
Creating a new IED into SAB600 project
5.
Check the default settings in the SCL Import view and change the settings if they
are not suitable.
The default settings in the SCL Import dialog should be correct in most cases.
6.
Click Import to import the SCD file.
7.
Check the IP address on the IEC 61850 subnetwork and change it if needed.
When the SCD file is directly exported from PCM600, it uses the IP address of the
PCM600 computer, not the COM600S.
The communication towards the protection relays is now ready. For information on how
to finalize the single-line diagram and enable parameter setting through COM600S HMI,
see COM600S documentation.

Using the Web HMI

WHMI is disabled by default, and has to be activated in the protection relay configuration.
As secure communication is enabled by default, the WHMI must be accessed from a Web
browser using the HTTPS protocol.
1.
To enable the WHMI, select Main menu/Configuration/HMI/Web HMI mode
via the LHMI.
2.
Reboot the relay for the change to take effect.
3.
Log in with the proper user rights to use the WHMI.
1MAC108982-MB E
615 series ANSI
Engineering Manual