1MRK 511 286-UUS A
14.1.2.1
Application manual
Station HSI
MicroSCADA
GOOSE
IED
IED
A
A
Control
Protection
IEC05000734 V1 EN
Figure 140:
Example of a broadcasted GOOSE message

Horizontal communication via GOOSE

GOOSE messages are sent in horizontal communication between the IEDs. The
information, which is exchanged, is used for station wide interlocking, breaker failure
protection, busbar voltage selection and so on.
The simplified principle is shown in
IED1 has decided to transmit the data set it forces a transmission via the station bus. All
other IEDs receive the data set, but only those who have this data set in their address list
will take it and keep it in an input container. It is defined, that the receiving IED will take
the content of the received data set and makes it available for the application
configuration.
Station communication
IED
IED
A
A
Control and protection
Control
Figure 141
and can be described as follows. When
Section 14
Gateway
IED
A
Protection
en05000734.vsd