Section 5 Protection Relay's Physical Connections; Inputs; Energizing Inputs; Differential Currents - ABB RELION 611 Series Applications Manual

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757455 E
Section 5
5.1
5.1.1
5.1.1.1
5.1.1.2
5.1.2
REB611
Application Manual
Protection relay's physical connections

Inputs

Energizing inputs

Differential currents

The protection relay can also be used in single or two-phase
applications by leaving one or two energizing inputs unoccupied.
However, at least terminals X120:7-8 must be connected.
Table 16:
Differential current inputs included in configuration A
Terminal
X120:7-8
X120:9-10
X120:11-12

Residual current

Table 17:
Residual current input included in configuration A
Terminal
X120:13-14

Auxiliary supply voltage input

The auxiliary voltage of the protection relay is connected to terminals X100:1-2. At
DC supply, the positive lead is connected to terminal X100:1. The permitted auxiliary
voltage range (AC/DC or DC) is marked on the top of the LHMI of the protection
relay.
Table 18:
Auxiliary voltage supply
Terminal
X100:1
X100:2
Protection relay's physical connections
Description
IL1
IL2
IL3
Description
Io
Description
+ Input
- Input
Section 5
63

Advertisement

Table of Contents
loading

Table of Contents