Power Consumption Example 2; Cooling; Library Electronics Control Module; Power Consumption Example - Oracle StorageTek SL3000 System Assurance Manual

Hide thumbs Also See for StorageTek SL3000:
Table of Contents

Advertisement

Cooling

Table 5–12
Quantity
1
16
--
Emissions: 933W x 0.02497 = 23.3 Kg of CO
Power consumption: 933W x 3.412 = 3,183 Btu/hr

Power Consumption Example 2

Using the maximum continuous values for the following components:
Table 5–13
Quantity
1
8
1
8
1
3
--
Emissions: 1,771W x 0.02497 = 44.2 Kg of CO
Power consumption: 1,771W x 3.412 = 6,043 Btu/hr
Cooling
Cooling within the SL3000 library is divided into three areas:
Electronics control module
Tape drives
DC power supplies

Library Electronics Control Module

Two fans, located to the right of the electronics control module, provide cooling for the
electronics in the library. Air is drawn from the sides of the library and flows through
the fans to the rear of the library.
The library controller card (HBCR) monitors these fans for proper operation.
An amber Fault indicator is on the fan assembly to indicate a failure.
While there are two dedicated fans, one fan is sufficient to provide adequate cooling
for the library and the electronics. The fans can be replaced without interfering with
library operations. Therefore, replace a defective fan when it is detected.
5-8 StorageTek SL3000 Systems Assurance Guide

Power Consumption Example

Component Description
SL3000 Base (including one ECM, one robot, one CAP)
LTO4 Tape Drives
Total
Power Consumption Example
Component Description
SL3000 Base (including one ECM, one robot, one CAP)
T9840D Tape Drives
Drive Expansion Module
T10000C Tape Drives
Cartridge Expansion Module
CAPs (3 at 10 Watts each)
Total
2
2
Watts
197
736
933
Watts
197
800
--
744
--
30
1,771