2N Power Configuration; Dc Power Supplies - Oracle StorageTek SL3000 System Assurance Manual

Hide thumbs Also See for StorageTek SL3000:
Table of Contents

Advertisement

DC Power Supplies

Limited support for T9840 and T10000 drives and no redundant TallBot support

2N power configuration

Offers both AC and DC power redundancy
Consists of two PDUs (per Base module or DEM) for AC redundancy, with a set of
DC power supplies for each PDU
Provides N DC power supplies per PDU
Requires two separate AC input sources per Base module or DEM
Required for redundant TallBot and redundant electronics support
2N+1 power configuration
Offers both AC and DC power redundancy with additional DC redundancy
Consists of two PDUs (per Base module or DEM) for AC redundancy, with
additional DC power supplies for each PDU
Provides N+1 DC power redundancy for each PDU (except the second PDU only
has N DC power supply redundancy for the TallBot)
Requires two separate AC input sources per Base module or DEM
Supports redundant TallBot and redundant electronics
DC Power Supplies
There are two types of DC power supplies:
Load sharing 1200W DC — used for the robotics unit and tape drives
200W cPCI — used for the electronics control module
5-2 StorageTek SL3000 Systems Assurance Guide