Fire Suppression Planning

Fire Suppression Planning
The library does not ship with a fire suppression system, but each module has a 5 cm
(2 inch) diameter nozzle opening (see
1.2 mm (0.048 inch) thick, cover the openings and can be drilled to custom fit nozzles.
Nozzles must be clear of robotic operations and cannot protrude more than 1.9 cm
(0.75 inches) into the library. Professional Services can assist with fire suppression
planning (contact your Oracle sales representative).

Cable Routing

The SL3000 library has rear door cut-outs on both the top and bottom of the door to
allow for cable routing. The cut-out is a 2.5 cm (1 inches) opening that runs 73 cm (29
inches) along the length of the door with cable routing hardware and reliefs available.
When routing cables, make sure to include locations for power, drive interface, library
control, and Ethernet cables. As a best practice, route power cables through one
cut-out and signal cables through another cut-out.
Figure 7–3 Door Cable Routing Cutouts
Figure Legend:
Cable routing area
1.
Top/bottom view of rear door
2.

AC Power Configurations and Cables

SL3000 libraries require that the customer select one of the following single phase AC
power options for the Base module and DEM:
110 VAC, 50/60 Hz, at 20 Amps (range: 100–127 VAC, 50–60 Hz, 16 Amps)
240 VAC, 50/60 Hz, at 30 Amps (range: 200–240 VAC, 50–60 Hz, 24 Amps)
Make sure to plan for the locations of power cables and list the locations for their
associated circuit breakers. Cables must be ordered for the appropriate power
configuration. Order one power cord per PDU installed:
N+1: One power cord for the Base module and an additional power cord for the
DEM (if installed).
2N or 2N+1: Two power cords for the Base module and two additional power
cords for the DEM (if installed).
7-6 StorageTek SL3000 Systems Assurance Guide
The Base module and DEM have two square cut-outs on the
Note:
rear door. These are only for PDU power source cables, not for general
cable routing.
Figure
7–1). Plates, 7 cm (2.75 inch) square and