Drive Duty Modes; Drive Parameters - YASKAWA CIPR-GA70C Series Initial Steps

High performance type
Hide thumbs Also See for CIPR-GA70C Series:
Table of Contents

Advertisement

12 Drive Control, Duty Modes, and Programming
Control Method
A1-02 Setting
V/f
(default)
OLV
EZOLV

Drive Duty Modes

The drive has two duty modes from which to select for the application: Heavy Duty (HD) and Normal Duty (ND).
The duty rating switches to HD2 or ND2 when E1-01 [Input AC Supply Voltage] ≥ 460 V. These specifications are
different between HD1/HD2 and ND1/ND2:
• The input power kVA
• The maximum applicable motor output
• The rated input current
• The rated output capacity
• The rated output current
Refer to
Table 12.1
for information about the differences between HD and ND ratings.
E1-01 Setting
Duty Rating
Input Voltage
• ≥ 200 V and < 240 V
Heavy Duty Rating 1
(HD1)
• ≥ 380 V and < 460 V
Heavy Duty Rating 2
≥ 460 V and < 480 V
(HD2)
Normal Duty Rating
• ≥ 200 V and < 240 V
1
• ≥ 380 V and < 460 V
(ND1)
Normal Duty Rating
2
≥ 460 V and < 480 V
(ND2)

Drive Parameters

Refer to the following table when setting the most important parameters.
Note:
Users can change parameters with "RUN" in the "No." column during Run.
No.
(Hex.)
A1-00
Language Selection
(0100)
RUN
A1-02
Control Method Selection Sets the control method for the drive application and the motor.
(0102)
A1-03
Initialize Parameters
(0103)
b1-01
Frequency Reference
Selection 1
(0180)
EN 26
• General variable-speed
0
• Operating more than one motor from one drive
• When replacing the motor without motor parameter values.
• General variable-speed
2
• High precision and speed control without speed feedback
• General variable-speed
8
• No high precision, no speed control, and no speed feedback
Table 12.1 Drive Duty Modes
C6-01
Setting
0
1
Name
Sets the language for the LCD keypad.
0: English, 1: Japanese, 2: German, 3: French, 4: Italian, 5: Spanish, 6: Portuguese,
7: Chinese, 8: Czech, 9: Russian, 10: Turkish, 11: Polish, 12: Greek
0: V/f Control, 1: V/f Control w/ PG, 2: Open Loop Vector, 3: Closed Loop Vector,
4: Advanced Open Loop Vector, 5: PM Open Loop Vector,
6: PM Advanced Open Loop Vector, 7: PM Closed Loop Vector, 8: EZ Vector Control
Sets parameters to default values.
0: No Initialization, 1110: User Initialization, 2220: 2-Wire Initialization,
3330: 3-Wire Initialization
Sets the input method for the frequency reference.
0: Keypad, 1: Analog Input, 2: Memobus/Modbus Communications, 3: Option PCB,
4: Pulse Train Input
Main Applications
Application
• Extruder
• Conveyor
• Constant torque or high
overload capacity
• Fan
• Pump
• Blower
• Variable speed control
Description
YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps
Overload Tolerance
Default Carrier
(oL2 [Drive
Frequency
Overload])
150% rated output
2 kHz
current for 60 s
110% rated output
2 kHz Swing-PWM
current for 60 s

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga700

Table of Contents