YASKAWA CIPR-GA70C Series Initial Steps page 21

High performance type
Hide thumbs Also See for CIPR-GA70C Series:
Table of Contents

Advertisement

Terminal
S1-S8, SC, SN, SP
H1, H2, HC
RP, +V, -V, A1, A2, A3, AC
MP, FM, AM, AC
D+, D-, AC
MA, MB, MC, M1-M6
PS, E(G)
Crimp Ferrules
Attach an insulated sleeve to the wire when connecting crimp ferrules. Refer to
external dimensions and model numbers of the crimp ferrules.
Yaskawa recommends the CRIMPFOX 6 crimping tool from PHOENIX CONTACT.
Wire Gauge
mm
2
(AWG)
0.25 (24)
AI 0.25-8YE
0.34 (22)
AI 0.34-8TQ
0.5 (20)
AI 0.5-8WH,
AI 0.5-8OG
Line Voltage Drop
WARNING
Electrical Shock Hazard. The leakage current of drive models 4389A to 4675A, 2xxxB/C and 4xxxB/C is more
than 3.5 mA. The IEC/EN 61800-5-1: 2007 standard specifies that users must wire the power supply to automatically turn off
when the protective ground wire disconnects. Users can also connect a protective ground wire that has a minimum cross-
sectional area of 10 mm
2
(copper wire) or 16 mm
injury.
Be sure to think about line voltage drop before selecting wire gauges.
Select wire gauges that drop the voltage by 2% or less of the rated voltage. Increase the wire gauge and the cable
length when the risk of voltage drops increases.
Calculate line voltage drop with this formula:
Line voltage drop (V) =
Dynamic Braking Precautions
Connect braking units to drives with these conditions:
• Models with built-in braking transistors use terminals B1 and -
• Models without built-in braking transistors use terminals +3 and -.
NOTICE
Review the Braking Unit and Braking Resistor Unit Installation Manual TOBPC72060001 for wire gauge and
tightening torque information before connecting a dynamic braking option to the drive. Failure to obey can cause damage to the
drive and braking circuit.
Connect a regenerative converter or regenerative unit with terminals +1 and -.
NOTICE
Do not connect a braking resistor to terminals +1 or -. Failure to obey can cause damage to the drive circuitry.
YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps
Table 10.1 Wire Gauges
Bare Wire
Recommended
Gauge
mm
2
(AWG)
0.75
(18)
Figure 10.2 Crimp Ferrule Dimensons
Table 10.2 Crimp Ferrule Models and Dimensions
Model
L (mm)
12.5
12.5
14
2
(aluminum wire). Failure to obey these standards can cause death or serious
× wire resistance (Ω/km) × wiring distance (m) × motor rated current (A) × 10
Recommended
Applicable Gauge
mm
2
(AWG)
mm
• Stranded wire
0.2 to 1.0
(24 to 18)
• Solid wire
0.2 to 1.5
(24 to 16)
Table 10.2
L1 (mm)
8
8
8
10 Electrical Installation
Crimp Ferrule
Applicable Gauge
Gauge
mm
2
(AWG)
2
(AWG)
0.5
0.25 to 0.5
(20)
(24 to 20)
for the recommended
d1 (mm)
d2 (mm)
0.8
2.0
0.8
2.0
1.1
2.5
-3
EN
EN 21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga700