YASKAWA CIPR-GA70C Series Initial Steps page 27

High performance type
Hide thumbs Also See for CIPR-GA70C Series:
Table of Contents

Advertisement

No.
Name
(Hex.)
b1-02
Run Command Selection
1
(0181)
b1-03
Stopping Method
Selection
(0182)
b1-04
Reverse Operation
Selection
(0183)
C1-01
Acceleration Time 1
(0200)
RUN
C1-02
Deceleration Time 1
(0201)
RUN
C2-01
S-Curve Time @ Start of
Accel
(020B)
C2-02
S-Curve Time @ End of
Accel
(020C)
C2-03
S-Curve Time @ Start of
Decel
(020D)
C2-04
S-Curve Time @ End of
Decel
(020E)
C6-01
Normal / Heavy Duty
Selection
(0223)
C6-02
Carrier Frequency
Selection
(0224)
d1-01 to d1-16
Reference 1 to 16
(0280 - 0291)
RUN
d1-17
Jog Reference
(0292)
RUN
d2-01
Frequency Reference
Upper Limit
(0289)
d2-02
Frequency Reference
Lower Limit
(028A)
E1-01
Input AC Supply Voltage
(0300)
E1-04
Maximum Output
Frequency
(0303)
E1-05
Maximum Output Voltage Sets the maximum voltage for the V/f pattern.
(0304)
E1-06
Base Frequency
(0305)
E1-09
Minimum Output
Frequency
(0308)
E2-01
Motor Rated Current
(FLA)
(030E)
YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps
12 Drive Control, Duty Modes, and Programming
Sets the input method for the Run command.
0: Keypad, 1: Analog Input, 2: Memobus/Modbus Communications, 3: Option PCB
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
0: Ramp to Stop, 1: Coast to Stop, 2: DC Injection Braking to Stop,
3: Coast to Stop with Timer, 9: Stop with Constant Distance
Enables and disables reverse operation. Disable reverse operation in fan or pump
applications where reverse rotation is dangerous.
0: Reverse Enabled, 1: Reverse Disabled
Sets the length of time to accelerate from zero to maximum output frequency.
Sets the length of time to decelerate from maximum output frequency to zero.
Sets the time to start S-curve acceleration.
Sets the time to complete S-curve acceleration.
Sets the time to start S-curve deceleration.
Sets the time to complete S-curve deceleration.
Sets the duty rating of the drive.
0: Heavy Duty Rating, 1: Normal Duty Rating
Sets the carrier frequency for the transistors in the drive.
1: 2.0 kHz, 2: 5.0 kHz (4.0 kHz for AOLV/PM), 3: 8.0 kHz (6.0 kHz for AOLV/PM),
4: 10.0 kHz (8.0 kHz for AOLV/PM), 5: 12.5 kHz (10.0 kHz for AOLV/PM),
6: 15.0 kHz (12.0 kHz AOLV/PM), 7: Swing PWM 1 (Audible Sound 1),
8: Swing PWM 2 (Audible Sound 2), 9: Swing PWM 3 (Audible Sound 3),
A: Swing PWM 4 (Audible Sound 4), F: User Defined (C6-03 to C6-05)
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Sets the Jog frequency reference in the units from o1-03 [Frequency Display Unit
Selection]. Set H1-xx = 6 [MFDI Function Select = Jog Reference Selection] to use the Jog
frequency reference.
Sets maximum limit for all frequency references. This value is a percentage of E1-04
[Maximum Output Frequency].
Sets minimum limit for all frequency references. This value is a percentage of E1-04
[Maximum Output Frequency].
Sets the drive input voltage. Set this parameter to the nominal voltage of the AC power
supply.
Sets the maximum output frequency for the V/f pattern.
Sets the base frequency for the V/f pattern.
Sets the minimum output frequency for the V/f pattern.
Sets the motor rated current in amperes.
Description
EN
EN 27