YASKAWA CIPR-GA70C Series Initial Steps page 9

High performance type
Hide thumbs Also See for CIPR-GA70C Series:
Table of Contents

Advertisement

Note:
• Energize the drive with factory defaults to show the Initial Setup screen. Push
–Select [No] from the [Show Initial Setup Screen] setting to not display the Initial Setup screen.
• Push
from the Home screen to show drive monitors.
• Push
to set d1-01 [Reference 1] when the Home screen shows U1-01 [Frequency Reference] in LOCAL Mode.
• The keypad will show [Rdy] when the drive is in Drive Mode. The drive is prepared to accept a Run command.
• The drive will not accept a Run command in Programming Mode in the default setting. Set b1-08 [Run Command Select in PRG
Mode] to accept or reject a Run command from an external source while in Programming Mode.
–Set b1-08 = 0 [Disregard RUN while Programming] to reject the Run command from an external source while in Programming Mode
(default).
–Set b1-08 = 1 [Accept RUN while Programming] to accept the Run command from an external source while in Programming Mode.
–Set b1-08 = 2 [Allow Programming Only at Stop] to prevent changes from Drive Mode to Programming Mode while the drive is
operating.
Mode
Keypad Screen
Drive Mode
Monitors
Parameters
User Custom Parameters
Parameter Backup/Restore
Programming
Modified Parameters/Fault Log
Mode
Auto-Tuning
Initial Setup
Diagnostic Tools
YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps
Table 6.2 Drive Mode Screens and Functions
Sets monitor items to display.
Changes parameter settings.
Shows the User Parameters.
Saves parameters to the keypad as backup.
Shows modified parameters and fault history.
Auto-Tunes the drive.
Changes initial settings.
Sets data logs and backlight.
(Home) to show the HOME screen.
Function
6 Keypad
EN
EN 9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga700