FLOW: every activation of the digital input, after a delay time or from the activation of the
pump (start) or from the activation of the input itself (normal conditions), will cause the
deactivation of the relative circulation pump.
Once the digital input is deactivated, the circulation pump will start to work according to its
own regulation (automatic rearm) unless the maximum number of flow switch alarms is not
reached for automatic rearm, however the deactivation of the alarm will be possible only
with manual procedure (manual rearm).
The regulation parameters relative to the delivery 1 and 2 circulation pumps are present in the
MCCT thermal power plant controller while the parameters relative to the circulation pumps of the
auxiliary DHW circuit, solar panels 1 and 2 are present in the MCPS controller for solar panels.
Important parameters:
MCCT: Installer Menu
MCCT: Installer Menu
MCCT: Maintenance Menu
MCCT: Maintenance Menu
MCCT: Maintenance Menu
MCPS: Installer Menu
MCPS: Installer Menu
MCPS: Installer Menu
MCPS: Installer Menu
MCPS: Installer Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
9.7.3 Manual functioning mode
The c-pro CLIMA system allows to set manual functioning for the various uses.
In this state the devices are not governed by the automatic functions, but are however sensitive to
any alarms.
The manual activation of the devices replaces the regulation for the determined device, therefore
from now on gives origin to all automatic controllers for the activation of the system.
For example, if the zone valve is controlled manually, it will be interpreted by the system as
thermostatic activation causing the activation of the relative delivery circulation pump, the mixing
valve and the boiler/chiller etc.
The manual functioning of the devices is useful for the execution of functional tests on system start-
up or in case or probe breakage or other.
C-PRO CLIMA SISTEMA INSTALLER MANUAL
I/O Configuration
Delivery lines 1(2)
General parameters
General parameters
General parameters
I/O Configuration
General parameters
General parameters
General parameters
General parameters
Flow switches
Flow switches
Flow switches
(MCCT, MCZN, MCDE, MCPS modules)
Digital In
Pump DI n alr
Pumps flow switches
Pumps flow switches
Pumps flow switches
D In
Pumps alarm setup
Pumps alarm setup
Pumps alarm setup
Pumps alarm setup
Alr ON delay
Alr RUN delay
Auto reset n°
Page 87
Start
Run
Nr alarms/hour
Solar pump 1
Solar pump 2
DHW pump
AUX1 pump