Important parameters:
MCPS: Installer menu
MCPS: Installer Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
9.5.5 Control of the high and low temperature of the auxiliary circuit AUX1
Whenever the temperature of the AUX1 auxiliary circuit water exceeds or drops below the
minimum and maximum temperature values accepted for the system of the hysteresis value, then
the c-pro micro MCPS solar panels regulator will start special management cycles for these
emergencies:
-
High temperature protection: the high temperature protection intervention will trigger a
simple signal to the maintenance staff.
-
Low temperature protection: the low temperature protection will trigger the activation of the
circulation pump of the auxiliary circuit in order to ease heating of the circuit water. The
pump will remain on until the minimum temperature conditions are recovered.
Important parameters:
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
9.5.6 Management and setting of the periodic antilegionella cycle for the DHW
In order to disinfect the DHW tank from the proliferation of legionella bacteria due to the deposit of
DHW, the c-pro CLIMA system envisions the periodic management of anti-legionella cycles.
Depending on the type of system, it is possible to select daily, weekly or monthly antilegionella
cycles.
An anti-legionella cycle consists in taking, the temperature of the DHW tank to a temperature such
to destroy bacteria (standard to 70°C, but which can be set from parameter) for a long enough
period of time (standard at 60 minutes, but can be set from parameter) by activation of the boiler
and the DHW circulation pump.
These periodic cycles will help with respect to the Standards in force on the subject.
Important parameters:
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
MCPS: Maintenance Menu
C-PRO CLIMA SISTEMA INSTALLER MANUAL
General parameters
General parameters
Aux1 Management
Aux1 Management
Aux1 Management
Aux1 Management
(MCPS module)
Aux1 Management
Aux1 Management
Aux1 Management
Aux1 Management
tank (MCPS module)
General parameters
General parameters
General parameters
General parameters
General parameters
General parameters
General parameters
Aux1 Circuit
pumps alarm CFG
Setpoint
Hysteresis
Probe offset
Mode
HT setpoint
HT hyst.
LT setpoint
LT hyst.
Antilegionella
Antilegionella
Antilegionella
Antilegionella
Antilegionella
Antilegionella
Antilegionella
Page 82
AUX1 pump
Enable
Mode
Start hour
Day week
Day month
Setpoint
Duration