6.7 Configuration parameters

Below find a list of all configuration parameters contained in the MAINTENANCE menu and
INSTALLER managed by the MCZN application.
A brief description is supplied for every parameter, the range of acceptable values, unit of
measurement and the default value proposed.
The menus are structured following the logic given in the respective description paragraphs
and 7.4.4.
6.7.1 List of MAINTENANCE menu configuration parameters
Label
Zone A Maintenance
Regulation enabling
Temperature
Zone A Maintenance
Regulation enabling
Humidity
Zone A Maintenance
Regulation enabling
T.Ext.set var
Zone A Maintenance
Regulation enabling
T. integration
Zone A Maintenance
Temp. regulation
COMFORT [S]
Zone A Maintenance
Temp. regulation
ECONOMY [S]
Zone A Maintenance
Temp. regulation
COMFORT [W]
Zone A Maintenance
Temp. regulation
ECONOMY [W]
Zone A Maintenance
Temp. Regulation
ANTIFREEZE
Zone A Maintenance
Temp. regulation
Min Set Ofs
Zone A Maintenance
Temp. regulation
Max Set Ofs
Zone A Maintenance
Temp. regulation
Hysteresis
Zone A Maintenance
Temp. integration
Winter delta
C-PRO CLIMA SISTEMA INSTALLER MANUAL
Parameter description
ZONE A MAINTENANCE
Enabling of Zone A temperature regulation
Enabling of Zone A humidity regulation
Enabling of Zone A room setpoint "climatic curve"
function
Enabling of Zone A heating/cooling integration"
function (via MCDE module)
- --- = Function disabled
- S = Cooling integration (summer)
- W = Heating integration (winter)
- S+W = Cooling/heating integration
(summer + winter)
Zone A summer Comfort time band pre-defined
temperature set-point (expressed in °C)
Zone A summer Economy time band pre-defined
temperature set-point (expressed in °C)
Zone A winter Comfort time band pre-defined
temperature set-point (expressed in °C)
Zone A winter Economy time band pre-defined
temperature set-point (expressed in °C)
Anti-freeze time band temperature set-point in winter
mode
Zone A (expressed in °C)
Work temperature set-point maximum negative
variation by Zone A remote set-point variator
(expressed in °C)
Work temperature set-point maximum positive
variation by Zone A remote set-point variator
(expressed in °C)
Zone A room temperature regulation hysteresis
(differential) relative to the work set-point
(expressed in °C)
Difference between room temperature and work set-
point due to activation of the winter Zone A
"integration to heating" function (expressed in °C)
Page 45
Default
Min
YES
NO
NO
NO
NO
NO
---
---
23.0
10.0
26.0
10.0
19.0
10.0
16.0
10.0
3.0
-10.0
-5.0
-10.0
5.0
-10.0
1.0
0.0
1.0
0.0
7.4.3
Max
YES
YES
YES
S+W
30.0
30.0
30.0
30.0
30.0
10.0
10.0
99.9
10.0