Evco C-PRO CLIMA SYSTEMA Installer Manual page 34

Table of Contents

Advertisement

Delay time on activation of the alarms relative to the 1
Pumps flow switches
and 2 delivery flow switches with system in normal
Run
conditions (expressed in seconds)
Pumps flow switches
Maximum number of alarms/hour relative to delivery
Nr. alarms/hour
flow switches 1 and 2 for passage to manual rearm
Network
Temporary MCZN disabling/enabling
management
X = enabled
Zone modul.
O = not enabled
enabling
Functioning mode of the circulation pump 1
Maintenance L1
CONT. = continuous
Pump mode
TRICH. = on temperature request
Maintenance L1
Delay time on activation of the alarm relative to the
Pump management
circulation pump 1 (expressed in seconds)
Alarm delay
Maintenance L1
Delay time on switch on of the circulation pump 1
Pump management
(expressed in seconds)
ON delay
Maintenance L1
Delay time on switch-off value change of mixing valve 1
Pump management
(expressed in seconds)
OFF delay
Maintenance L1
Delay time on opening value change of mixing valve 1
Pump management
(expressed in seconds)
Mix.vlv. delay
Maintenance L1
Delay time on activation of the chiller/heat pump
Pump management
(expressed in seconds)
CH-HP delay
Maintenance L1
Pump management
Enabling of the line 1 antigrip function
Antigrip enab.
Maintenance L1
Temp. regulation
L.T. line 1 summer delivery set-point (expressed in °C)
Setpoint S LT
Maintenance L1
Temp. regulation
H.T. line 1 winter delivery set-point (expressed in °C)
Setpoint W LT
Maintenance L1
Temp. regulation
H.T. line 1 summer delivery set-point (expressed in °C)
Setpoint S HT
Maintenance L1
H.T. line 1 winter delivery set-point
Temp. regulation
(expressed in °C)
Setpoint W HT
Offset (differential) to add to the delivery line 1 dew
Maintenance L1
point, calculated to obtain the delivery work set-point
T. regulation
value in Summer mode
Dew offset
(expressed in °C)
Summer mixing valve 1 functioning mode
Maintenance L1
- Closed
Mixing valve S
- Modulating
Mode
- Opened
Maintenance L1
Minimum external temperature in summer for the
Mixing valve S
calculation of the delivery 1 floating set-point (expressed
Min.Ext.T.
in °C)
Maintenance L1
Maximum external temperature in summer for the
Mixing valve S
calculation of the delivery 1 floating set-point (expressed
Max.Ext.T.
in °C)
Value of the floating delivery 1 set-point relative to the
Maintenance L1
minimum external temperature in Summer mode
Mixing valve S
(expressed in °C)
Setpoint 1
C-PRO CLIMA SISTEMA INSTALLER MANUAL
DELIVERY LINES
Page 34
5
0
3
0
O
X
TRICH.
CONT.
0
0
30
0
30
0
30
0
60
0
Yes
No
18.0
7.0
30.0
20.0
12.0
5.0
60.0
25.0
3.0
0.0
MODUL.
CLOSED
10.0
0.0
30.0
10.0
12.0
0.0
255
255
O
TRICH.
255
255
255
255
255
Yes
30.0
90.0
30.0
90.0
10.0
OPENED
30.0
60.0
40.0