Evco s.p.a. c-pro 3 clima sistema | installer manual ver.1.0 | code 144cp3cse104 page 1 of 92 c-pro 3 clima sistema climatic modules for the air conditioning and heating of buildings (92 pages)
Page 2
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Important Important Read this document carefully before the installation and before the use and follow all the additional information for the installation and for the electrical connection; keep this document close to the devices for future consultations.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 DESCRIPTION 2.1. Description c-pro 3 hecto and c-pro 3 hecto+ The following drawing shows the aspect of c-pro 3 hecto and of c-pro 3 hecto+. The following table shows the meaning of the parts of the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 2.2. Description c-pro 3 mega The following drawing shows the aspect of c-pro 3 mega. The following table shows the meaning of the parts of the controller. Part...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 2.3. Description c-pro 3 NODE mega The following drawing shows the aspect of c-pro 3 NODE mega. The following table shows the meaning of the parts of the controller.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 3.4. Installation On DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm (1.377 x 0.590 in). To install the devices operate as shown in the following drawing.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 ELECTRICAL CONNECTION 4.1. Electrical connection c-pro 3 hecto and c-pro 3 hecto+ 4.1.1. Meaning of the connectors of c-pro 3 hecto and of c-pro 3 hecto+ The following drawing shows the connectors of c-pro 3 hecto and of c-pro 3 hecto.
Page 15
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications and implementation guides manual (the document is available on the internet site www.modbus.org).
Page 16
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 polarize the network of the RS-485 port (560 Ω, 0.25 W); position micro-switches 2 and 3 on position ON to polarize the network of the RS-485 port (the network must be polarized by an element of the network same).
Page 17
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 normally open contact digital output 2 common digital output 3 normally open contact digital output 3 CO4/5 common digital outputs 4 and 5 normally open contact digital output 4 normally open contact digital output 5 Digital output 6 (electromechanical relay).
Page 18
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Digital output 6 (electromechanical relay). Terminal Meaning common digital output 6 normally open contact digital output 6 normally closed contact digital output 6 The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).
Page 19
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 The maximum length of the connecting cables of the PWM analog output is 1 m (3.280 ft); the one of the connecting cables of the 0-20 mA / 4-20 mA / 0-10 V analog outputs is instead of 30 m (98 ft).
Page 20
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 PROG Programming and debugging port. POWER SUPPLY Power supply. Terminal Meaning V≅ power supply controller (24 VAC / 20... 40 VDC) V≅ power supply controller (24 VAC / 20... 40 VDC) The maximum length of the connecting cables of the power supply of the controller is 30 m (98 ft).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 4.1.2. Example of electrical connection of c-pro 3 hecto The following shows an example of electrical connection of c-pro 3 hecto. To reduce the reflections on the signal transmitted through the cables connecting the devices each other, plug in the termination of the CAN port of the first and of the last element of the network.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 4.2. Electrical connection c-pro 3 mega and c-pro 3 NODE mega 4.2.1. Meaning of the connectors of c-pro 3 mega and of c-pro 3 NODE mega The following drawing shows the connectors of c-pro 3 mega and of c-pro 3 NODE mega.
Page 23
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft); also look at the Modbus specifications and implementation guides manual (the document is available on the internet site www.modbus.org).
Page 24
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 not connected D0 = B = - (terminal 0 of the transceiver) D1 = A = + (terminale 1 of the transceiver) not connected not connected not connected The maximum length of the connecting cables of the RS-485 port is 1,000 m (3,280 ft);...
Page 25
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 MICRO-SWITCH Micro-switch to: plug in the terminations of the RS-485 ports (120 Ω, 0.25 W); position micro-switch 1 on position ON to plug in the termination of the first RS-485 port and micro-switch 2 on position ON to plug in the termination of the second RS-485 port (plug in the termination of the first and of the last element of the network) polarize the network of the second RS-485 port (560 Ω, 0.25 W);...
Page 26
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 For the settings about the CAN port look at chapter 6 “CONFIGURATION”. Power supply user interface. Terminal Meaning ground power supply user interface (24 VDC, 120 mA max.) The maximum length of the connecting cables of the power supply of the user interface is 30 m (98 ft).
Page 27
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 normally open contact digital output 8 normally closed contact digital output 8 The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).
Page 28
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 digital input 7 common digital inputs The maximum length of the connecting cables of the digital inputs is 100 m (328 ft). The digital inputs can be used on condition that they are powered at 24 VAC / DC.
Page 29
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 The maximum length of the connecting cables of the power supply of the controller is 30 m (98 ft). Protect the power supply with a fuse rated 2.5A-T 250 V.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 4.2.2. Example of electrical connection of c-pro 3 mega The following drawing shows an example of electrical connection of c-pro 3 mega. To reduce the reflections on the signal transmitted through the cables connecting the devices each other, plug in the termination of the CAN port of the first and of the last element of the network.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 4.3. Electrical connection c-pro 3 EXP hecto and c-pro 3 EXP hecto+ 4.3.1. Meaning of the connectors of c-pro 3 EXP hecto and of c-pro 3 EXP hecto+ The following drawing shows the connectors of c-pro 3 EXP hecto and of c-pro 3 EXP hecto+.
Page 32
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 The maximum length of the connecting cables of the CAN port depends on the baud rate of the CANbus communication, as follows: 1,000 m (3,280 ft) with baud rate 20,000 baud...
Page 33
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 DIGITAL OUTPUTS In c-pro 3 EXP hecto+. Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays). Terminal Meaning CO1/2 common digital outputs 1 and 2 normally open contact digital output 1...
Page 34
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 The maximum length of the connecting cables of the PWM analog output is 1 m (3.280 ft); the one of the connecting cables of the 0-20 mA / 4-20 mA / 0-10 V analog outputs is instead of 30 m (98 ft).
Page 35
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 ANALOG INPUTS Analog inputs. Each analog input is configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric / 0-10 V transducers.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 4.3.2. Example of electrical connection of c-pro 3 EXP hecto The following drawing shows an example of electrical connection of c-pro 3 EXP hecto. To reduce the reflections on the signal transmitted through the cables connecting the devices each other, plug in the termination of the CAN port of the first and of the last element of the network.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 USER INTERFACE 5.1. Keyboard The following table shows the meaning of the keyboard. Button Preset function cancel, hereinafter also called “button ESC” move to left, hereinafter also called “button LEFT”...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 LED CANbus communication if it is lit, the device will be configured to communicate via CANbus with another device but the CAN communication will not have been set up...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 CONFIGURATION 6.1. Configuring a programmable controller 6.1.1. Configuring a built-in programmable controller To gain access to the procedure operate as follows: Make sure the power supply is switched on.
Page 41
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 To modify the real date and time operate as follows: From step 2, press and release button UP or button DOWN to select the voice Data e ora reale.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 6.1.2. Configuring a blind programmable controller The following procedures show an example of configuration of a blind programmable controller through a built-in programmable controller (in the example it is c-pro 3 mega) and through its user interface.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 6.2. Configuring an I / O expansion The following procedures show an example of configuration of an I / O expansion through a built-in programmable controller (in the example it is c-pro 3 mega) and through its user interface.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 6.3. Configuring a device through an user interface (Vgraph, Vtouch or Vroom) The following procedures show an example of configuration of a device through an user interface (in the example Vgraph) and through its user interface.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 6.4. List of configuration parameters 6.4.1. List of configuration parameters of c-pro 3 hecto and of c-pro 3 hecto+ Submenu Parameter Min. Max. Unit Preset Description information about the application project...
Page 47
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 connection among the passwords to gain access to the levels Parameters (2) one has to set [ press button password to gain access to Password Indi - - -...
Page 48
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Networks / CAN [ press button TSEG2 - - - reserved RIGHT to show it ] Networks / CAN [ press button - - - reserved RIGHT to...
Page 49
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Modbus communication time-out RS-485 network wired on the RS-485 port for the test of the remote values of the I / O Networks / Timeout (after this time...
Page 50
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 value of the password to gain access to -32768 32767 - - - level 5 enabling the password to gain access to Password Level 5: level 5 to gain access to level 5 one...
Page 51
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Math status not in error Diagnostic Math parameter available in read only modality in error (because of overflow, underflow, division by zero or NaN) result of the copy of the parameters from the...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 6.4.2. List of configuration parameters of c-pro 3 mega and of c-pro 3 NODE mega Submenu Parameter Min. Max. Unit Preset Description information about the application project Info...
Page 54
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 time-out of the CANbus communication for Parameters (2) the test of the remote values of the I / O [ press button I/O Timeout (after this time without...
Page 55
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Parameters (2) [ press button RIGHT to Contrast - - - display contrast show it; not available in the blind versions ] Parameters (2) [ press button RIGHT to...
Page 57
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Networks / CAN [ press button BTR(1) - - - reserved RIGHT to show it ] local (or of the controller) BACnet MS/TP Networks / BMS MAC ID...
Page 58
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Modbus communication stop bit number in a RS-485 network wired on the first RS-485 Networks / Stop - - - - - - - - - 1 BIT...
Page 59
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 enabling the password to gain access to level 1 to gain access to level 1 one - - - - - - - - - has not to set any password...
Page 60
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 time-out of the passwords to gain access to the levels (after this time since the last Password Timeout operation with the buttons, to gain access to the level one has to set a password again, if...
Page 61
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 result of the copy of the parameters from the controller to the programming key EVKEY10 and vice versa Diagnostic Key Par parameter available in read only modality operation...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 6.4.3. List configuration parameters c-pro hecto c-pro 3 EXP hecto+ Submenu Parameter Min. Max. Unit Preset Description information about the application project Info PROJ parameter available in read only modality...
Page 64
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 Networks / CAN [ press button TSEG1 - - - reserved RIGHT to show it ] Networks / CAN [ press button TSEG2 - - - reserved RIGHT to...
Page 65
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 parameter available in read only modality number of packages in error Debug [ CAN bus ] parameter available in read only modality number of packages in overflow reading the power supply voltage of the...
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vgraph since at the front of the interface one can apply both the plates CPVP* by EVCO (to order separately, made in plastic material and available in two different colorations, white and black) and the numerous plates series "Living"...
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vtouch since at the front of the interface one can apply both the plates CPVP* by EVCO (to order separately, made in plastic material and available in two different colorations, white and black) and the numerous plates series "Living"...
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vroom since at the front of the interface one can apply both the plates CPVP* by EVCO (to order separately, made in plastic material and available in two different colorations, white and black) and the numerous plates series "Living"...
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 ACCESSORIES 8.1. Programming kit EVIF20TUXI 8.1.1. Introduction EVIF20TUXI is a programming kit. Through the kit it is possible to program the controllers with the application software realized through UNI-PRO 3.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 8.1.3. Size Size is in mm (in). 8.1.4. Connection to the Personal Computer Operate as follows: Plug in an end of the TTL cable into the TTL port of the serial interface.
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 The following table shows the meaning of the parts of the key. Part Meaning telephone connector connector for power supplier EVPS 8.2.3. Size Size is in mm (in).
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 TECHNICAL DATA 9.1. Technical data Purpose of control: programmable controller for applications in refrigeration, ventilation and air conditioning. Construction of control: electronic control device to be incorporated. Box: self-extinguishing grey UL94 V0.
Page 76
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 The maximum lengths of the connecting cables are the followings: • power supply controller: 30 m (98 ft) • analog inputs: 100 m (328 ft) • power supply transducers: 100 m (328 ft) •...
Page 77
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 24 VAC (±15%), 50 / 60 Hz (±3 Hz), 30 VA max. isolated or 20... 40 VDC, 22 W max. isolated, supplied by a class 2 circuit. The devices incorporate a protection against the reversal of polarity.
Page 78
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 4 non optoisolated inputs, of 4 non optoisolated inputs, of which 3 configurable via which 3 configurable via configuration parameter for configuration parameter for PTC / NTC / Pt 1000 probes...
Page 79
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 0-5 V ratiometric / 0-10 V analog inputs Input resistance: ≥ to 10K Ω. Accuracy: ±0.5% of the full scale. Resolution: 0.01 V. Conversion time: 100 ms. Protection: against the reversal of the polarity.
Page 80
EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204 PWM analog outputs Driving power supply: 24 VDC (+16% -25%), 50 mA max. Frequency: the same as the one of the phase powering the device. Protection: no protection.
Page 85
EVCO does not take any responsibility about damages coming by the non-observance of the additional information. EVCO reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
Need help?
Do you have a question about the c-pro 3 Series and is the answer not in the manual?
Questions and answers