8.6 Configuration parameters
Below find a list of all configuration parameters contained in the MAINTENANCE menu
(maintenance technician) and INSTALLER managed by the MCPS application.
A brief description is supplied for every parameter, the range of acceptable values, unit of
measurement and the default value proposed.
The menus are structured following the logic given in the respective description paragraphs
and 9.4.7.
8.6.1 List of MAINTENANCE menu configuration parameters
Label
General parameters
Antigrip
Execution day
General parameters
Antigrip
Execution hour
General parameters
Probes offset
Upper DHW tank
General parameters
Probes offset
Lower DHW tank
General parameters
Antilegionella
Enable
General parameters
Antilegionella
Mode
General parameters
Antilegionella
Start hour
General parameters
Antilegionella
Day week
General parameters
Antilegionella
Day month
General parameters
Antilegionella
Setpoint
General parameters
Antilegionella
Duration
Panels Maintenance
Periodic cycle
Interval
Panels
MAINTENANCE
Periodic cycle
Duration
C-PRO CLIMA SISTEMA INSTALLER MANUAL
Parameter description
GENERAL PARAMETERS
Antigrip function start day
Antigrip function start time
Boiler upper probe calibration (offset)
(expressed in °C)
Boiler lower probe calibration (offset)
(expressed in °C)
Enabling of antilegionella cycle
Antilegionella cycle activation mode
- MONTH = Monthly
- WEEK = Weekly
- DAY = Daily
Time of antilegionella cycle start
(expressed in hours:minutes)
Day of the week for antilegionella cycle start
(if weekly activation enabled)
Day of the month for antilegionella cycle start
(if monthly activation enabled)
Water temperature set-point during the antilegionella
cycle
(expressed in °C)
Duration of the antilegionella cycle
(expressed in minutes)
MAINTENANCE
Interval between two periodic activation cycles of the
solar panels circulation pumps
(expressed in minutes)
Duration of the periodic activation cycle of the solar
panels circulation pumps
(expressed in minutes)
Page 64
Default
Min
Monday
Sunday
2:00
0:00
0.0
-10.0
0.0
-10.0
No
No
WEEK
MONTH
16:00
0:00
Wednes-
Sunday
day
15
1
70.0
0.0
60
0
30
0
10
0
9.4.6
Max
Saturday
23:00
10.0
10.0
Yes
DAY
23:00
Saturday
28
150.0
255
255
255
Need help?