Page 1
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.1 | Code 114CP3UKE114 c-pro 3 micro and c-pro 3 kilo PROGRAMMABLE CONTROLLERS ENGLISH HARDWARE MANUAL ver. 1.1 CODE 114CP3UKE114 page 1 of 62...
Page 2
EPK3LXP I/O expansions do not need any updating. Best regards, EVCO S.p.A. EVCO S.p.A. | Via Feltre 81, 32036 Sedico (BL) ITALY | phone +39 0437 8422 | fax +39 0437 83648 | email info@evco.it | web www.evco.it VAT number IT00769310251...
Page 3
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Important Important Read this document carefully before the installation and before the use and follow all the additional information for the installation and for the electrical connection;...
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 INTRODUCTION 1.1. Introduction c-pro 3 micro and c-pro 3 kilo are two families of programmable controllers. The family consists of: programmable controllers (c-pro 3 micro, c-pro 3 micro+, c-pro 3 kilo and c-pro 3 kilo+) I / O expansions (c-pro 3 EXP micro, c-pro 3 EXP micro+, c-pro 3 EXP kilo and c-pro 3 EXP kilo+).
(not available in the blind versions) analog inputs 7... 9, digital inputs 6... 9 and analog outputs 4... 6 (available in models c-pro 3 micro+ and c-pro 3 kilo+ only) analog inputs 1... 6, digital inputs 1... 5 and analog outputs 1... 3...
Page 7
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 RS-485 port with Modbus master communication protocol (available in models c-pro 3 micro+ and c-pro 3 kilo+ only) micro-switch to plug in the termination of the RS-485 port with Modbus master communication protocol (available in...
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 2.2. Description I/O expansions The following drawing shows the aspect of the I/O expansions. The following table shows the meaning of the parts of the expansion.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 SIZE AND INSTALLATION 3.1. Size programmable controllers 4 DIN modules; size in mm (in). 3.2. Size I/O expansions 4 DIN modules; size in mm (in).
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 3.3. Installation On DIN rail 35.0 x 7.5 mm (1.377 x 0.295 in) or 35.0 x 15.0 mm (1.377 x 0.590 in). To install the devices operate as shown in the following drawing.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 ELECTRICAL CONNECTION 4.1. Connectors programmable controllers The following drawing shows the connectors of c-pro 3 micro and of c-pro 3 kilo. The following drawing shows the connectors of c-pro 3 micro+ and of c-pro 3 kilo+.
Page 12
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Models with 7 electromechanical relays and 2 solid state relays Models with integrated unipolar stepper electronic expansion valves driver page 12 of 62...
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 4.2. Connectors I/O expansions The following drawing shows the connectors of c-pro 3 EXP micro and of c-pro 3 EXP kilo. The following drawing shows the connectors of c-pro 3 EXP micro+ and of c-pro 3 EXP kilo+.
Page 14
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Models with 7 electromechanical relays and 2 solid state relays page 14 of 62...
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 4.3. Meaning of connectors The following tables show the meaning of the connectors. Digital outputs 1… 7 Electromechanical relays. Terminal Meaning normally open contact digital output 6 (3 res. A @ 250 VAC) normally closed contact digital output 7 (3 res.
Page 16
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 normally open contact digital output 9 (3 res. A @ 250 VAC in case of electromechanical relay; 24 VAC/DC, 0,6 A max in case of solid state relay)
Page 17
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 RS-485 port RS-485 port with Modbus master communication protocol (with network already polarized internally). Terminal Meaning ground A / + terminal 1 of the transceiver...
Page 18
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Analog inputs 7... 9, digital inputs 6... 9 and analog outputs 4... 6 Terminal Meaning common analog inputs and analog outputs analog input 7 (configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V...
Page 19
Terminal Meaning power supply controller (12 VAC in c-pro 3 micro and in c-pro 3 micro+, 24 VAC / 20... 30 VDC in c-pro 3 kilo and in V≅ + c-pro 3 kilo+); if the controller is powered in alternating current, connect the phase power supply controller (12 VAC in c-pro 3 micro and in c-pro 3 micro+, 24 VAC / 20...
Page 20
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 The following table shows the function codes supported by the controller. Function Meaning code FC 01 read coils FC 02 read discrete inputs...
Page 21
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 USB port OTG USB port. Analog inputs 1... 6, digital inputs 1... 5 and analog outputs 1... 3 Terminal Meaning analog input 1 (configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V...
Page 22
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 The maximum length of the connecting cables is: 100 m (328 ft) for the analog inputs 100 m (328 ft) for the power supply of the transducers 100 m (328 ft) for the digital inputs 1 m (3.280 ft) for the PWM analog outputs...
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 4.3.1. Example of electrical connection The following drawing shows an example of electrical connection of c-pro 3 kilo+ with c-pro 3 EXP kilo+ and with Vgraph.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 For the devices powered at 24 VAC, it is necessary the phase powering the device is the same powering the remaining devices in the network.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 USER INTERFACE 5.1. Keyboard The following table shows the meaning of the keyboard. Button Preset function cancel, hereinafter also called “button ESC” move to left, hereinafter also called “button LEFT”...
Page 26
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 LED CANbus communication if it is lit, the device will be configured to communicate via CANbus with another device but the CAN communication...
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 CONFIGURATION 6.1. Configuring a programmable controller 6.1.1. Configuring a built-in programmable controller To gain access to the procedure operate as follows: Make sure the power supply is switched on.
Page 28
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 To modify the real date and time operate as follows: From step 2, press and release button UP or button DOWN to select the voice Data e ora reale.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 6.1.2. Configuring a blind programmable controller The following procedures show an example of configuration of a blind programmable controller through a built-in programmable controller (in the example it is c-pro 3 kilo) and through its user interface.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 6.2. Configuring an I / O expansion The following procedures show an example of configuration of an I / O expansion through a built-in programmable controller (in the example it is c-pro 3 kilo) and through its user interface.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 6.3. Configuring a device through an user interface (Vgraph, Vtouch, Vroom or Vcolor) The following procedures show an example of configuration of a device through an user interface (in the example Vgraph) and through its user interface.
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 6.4. List of configuration parameters Submenu Parameter Min. Max. Unit Preset Description information about the application project Info PROJ parameter available in read only modality...
Page 33
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 kind of probe analog input 2 PTC probe NTC probe 0-20mA = 0-20 mA transducer 4-20mA = 4-20 mA transducer 0-5V 0-5 V ratiometric transducer...
Page 35
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 analog inputs time-out (after this time without Parameters (1) AI Err Time communication with an analog input, the controller signals the analog input error)
Page 36
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 driving mode of the stepper motor full step 2 phases on Parameters (1) EEV_DrvMode - - - full step 1 phase on half step...
Page 37
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Parameters (2) [ press button kind of backlight RIGHT to the backlight is never lit show it; not the backlight is always lit...
Page 38
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Parameters (2) [press button RIGHT to date format show it; not D-M-Y day, month and year available in the Date format - - -...
Page 40
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Networks / CAN CAN bus status status OK [ press button Bus Status parameter available in read only modality WARNING warning RIGHT to...
Page 41
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Modbus communication baud rate in a RS-485 network wired on the RS-485 port with Modbus slave communication protocol 1200 1,200 baud 2400 2,400 baud...
Page 42
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Modbus communication baud rate in a RS-485 network wired on the RS-485 port with Modbus master communication protocol 1200 1,200 baud 2400 2,400 baud...
Page 43
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 enabling the password to gain access to level 2 to gain access to level 2 one - - - - - - - - -...
Page 44
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 clock status not in error Diagnostic parameter available in read only modality in error loss of data disab disabled stack status Diagnostic STACK...
Page 45
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 Free stack parameter available in read only modality number of packages in reception reading the power supply voltage of the Debug 5V probe...
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vgraph since at the front of the interface one can apply both the plates CPVP* by EVCO (to order separately, made in plastic material and available in two different colorations, white and black) and the numerous plates series "Living"...
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vtouch since at the front of the interface one can apply both the plates CPVP* by EVCO (to order separately, made in plastic material and available in two different colorations, white and black) and the numerous plates series "Living"...
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vroom since at the front of the interface one can apply both the plates CPVP* by EVCO (to order separately, made in plastic material and available in two different colorations, white and black) and the numerous plates series "Living"...
Also the necessity to customize the interface, in order to integrate it aesthetically in residential and commercial environments, is satisfied by Vcolor since at the front of the interface one can apply both the plates CPVP* by EVCO (to order separately, made in plastic material and available in two different colorations, white and black) and the numerous plates series "Living"...
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 TECHNICAL DATA 8.1. Technical data Purpose of control: programmable controller for applications in refrigeration, ventilation and air conditioning. Construction of control: electronic control device to be incorporated.
Page 55
According to the model: • male Micro-Fit connectors (power supply, inputs, analog outputs, CAN port and RS-485 ports) in c-pro 3 micro, c-pro 3 micro+, c-pro 3 EXP micro and c-pro 3 EXP micro+ • male extractable clamp terminal blocks with pitch 3.5 mm (0.137 in; power supply, inputs, analog outputs, CAN port and RS-485 ports) for conductors up to 1.5 mm²...
Page 56
EN / IEC 60730-1. 12 VAC (+10%, -15%), 50 / 60 Hz, 20 VA max. supplied by a class 2 circuit in c-pro 3 micro, c-pro 3 micro+, c-pro 3 EXP micro and c-pro 3 EXP micro+; 24 VAC (+10%, -15%), 50 / 60 Hz, 35 VA max.
Page 57
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 NTC analog inputs (10K Ω @ 25 ° C, 77 ° F) β3435. Kind of sensor: Working range: from -50 to 120 ° C (-58 to 248 ° F).
Page 58
• nothing (blind version). 3 non optoisolated outputs in c-pro 3 micro, c-pro 3 kilo, c-pro 3 EXP micro and c-pro 3 EXP kilo: • 2 outputs configurable via configuration parameter for PWM / 0-10 V signal •...
Page 59
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 0-20 mA / 4-20 mA analog outputs 40... 300 Ω. Input resistance: Accuracy: ±3% of the full scale. Resolution: 0.05 mA. Conversion time: 1 s.
Page 60
EVCO S.p.A. c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104 In c-pro 3 micro and c-pro 3 kilo: • 1 non optoisolated OTG USB port (for programming and debug) • 1 non optoisolated CAN port with CANbus communication protocol •...
Page 61
EVCO does not take any responsibility about damages coming by the non-observance of the additional information. EVCO reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
Need help?
Do you have a question about the c-pro 3 micro and is the answer not in the manual?
Questions and answers