Functional Description
When the motor is running, a current reduction might indicate a malfunction in the load.
Underload protection recognizes mechanical problems, such as a blocked flow or loss of
back pressure in a pump, or a broken drive belt or drive shaft.
Refer to the underload protection limit – the left vertical line in the Underload and Jam Trip
Function example. In the example, the underload trip is set at 60% of FLA. The protective
device can be configured for underload alarm and underload trip.