4 Protective Elements
4.13 26/38/49 – RTD Protection Module
RTD . Any Group
All pickups, timeout alarms and trips of the groups are connected by an OR-gate in order to generate a group pickup, a group timeout alarm or and group trip.
RTD . Alarm WD Group
RTD . Alarm MB Group
RTD . Alarm LB Group
RTD . Alarm Aux Group
RTD . TimeoutAlmWDGrp
RTD . TimeoutAlmMBGrp
RTD . TimeoutAlmLBGrp
RTD . TimeoutAlmAuxGrp
RTD . Trip WD Group
RTD . Trip MB Group
RTD . Trip LB Group
RTD . Trip Aux Group
Collective Timeout Alarm Signal
All RTD sensor timeout alarms and all group timeouts are OR-connected.
RTD . Timeout Alarm
All timeout alarms are OR connected to a collective alarm.
RTD . TimeoutAlmWDGrp
RTD . TimeoutAlmAuxGrp
Collective Trip Signal
All RTD group trip signals are OR-connected, resulting in the collective trip signal »RTD .
Trip«.
RTD . Trip
All trips are OR connected to a collective trip signal.
RTD . Trip WD Group
RTD . Trip MB Group
RTD . Trip LB Group
RTD . Trip Aux Group
184
OR
OR
OR
OR
OR
www.eaton.com
RTD_E02
RTD . Alarm Any Group
RTD . TimeoutAlmAnyGrp
RTD . Trip Any Group
RTD_E94
RTD . Alarm
RTD_E95
RTD . Trip
14