Eaton EMR-3MP0 Installation, Operation And Maintenance Manual page 249

Motor relay
Table of Contents

Advertisement

Under Load Protection: 37[x]
Threshold
Dropout Ratio
t
Operating Time
Starting from I lower than 0.8 x setting
value
Disengaging Time
Starting from I ≥ 2 times setting value
Mechanical Load Shedding: MLS
Pickup Threshold
Pickup Delay
Dropout Threshold
Dropout Delay
Start Delay Timers
Start Delay (common timers)
Operating Times
for IOC, GOC, JAM
for Underload, Generic 1-5
EMR-3MP0
Accuracy
±1.5% of the setting value or 1% In
103% or 0.5% In
DEFT
±1% or ±10 ms
<35 ms
<24 ms
Accuracy
±1.5% of the setting value or 1% In
DEFT
±1% or ±10 ms
±1.5% of the setting value or 1% In
DEFT
±1% or ±10 ms
Accuracy
±1% or ±10 ms
<35 ms
<60 ms
www.eaton.com
10 Technical Data EMR-3MP0
10.1 Tolerances / Specifications
249