Eaton EMR-3MP0 Installation, Operation And Maintenance Manual page 255

Motor relay
Table of Contents

Advertisement

Fast Transient Disturbance Immunity Test (Burst)
IEC 61000-4-4
class 4
Surge Immunity Test (Surge)
IEC 60255-22-5
IEC 60255-26
IEC 61000-4-5
class 4
class 3
Electrical Discharge Immunity Test (ESD)
IEC 60255-22-2
IEC 60255-26
IEC 61000-4-2
class 3
Radiated Radio Frequency Electromagnetic Field Immunity Test
IEC 60255-22-3
IEC 60255-26
IEC 61000-4-3
Immunity to Conducted Disturbances Induced by Radio Frequency Fields
IEC 61000-4-6
IEC 60255-26
class 3
Power Frequency Magnetic Field Immunity Test
IEC 61000-4-8
IEC 60255-26
EMR-3MP0
Within one circuit
Circuit to ground
Communication cables to ground
Air discharge
Contact discharge
26 MHz – 80 MHz
80 MHz – 1 GHz
1 GHz – 3 GHz
150kHz - 80MHz
continuous
3 sec
www.eaton.com
11 Appendix
11.1 Standards
2 kV
4 kV
2 kV
8 kV
6 kV
10 V/m
35 V/m
10 V/m
10 V
30 A/m
300 A/m
255