Motor Protection Curves - Eaton EMR-3MP0 Installation, Operation And Maintenance Manual

Motor relay
Table of Contents

Advertisement

4 Protective Elements
4.4 Ultimate Trip Current
4.4.1

Motor Protection Curves

Ultimate trip
based on % of
full-load
amperes
(100% shown)
I²T curves
(I is an effective
current including
I1 and kI2.)
Fig. 39: Motor Protection Curve (Example 1).
160
multiples of FLA
www.eaton.com
Maximum allowable
stalll time
(30 sec cold start)
(15 sec cold start)
(10 sec cold start)
(5 sec cold start)
Based upon locked
rotor current of 6.1
times full-load amps
Instantaneous
overcurrent set at
12 times full-load
amperes
Instantaneous
overcurrent start
delay set for
2 cycles
EMR-3MP0